3.2.4 Wind load control
The IS 9100 is especially suited for external doors that are
exposed to changing wind loads or internal doors separating
rooms in which pressure differences might occur. In
automatic mode, the wind load control monitors the actual
speed and will compensate for it if the speed deviates from
the set value. In combination with the Upgrade Card Full
Energy the drive unit can provide up to 150 N at the main
closing edge, which can then be used to compensate for
environmental influences.
The closing process during the last 5° can be additionally
supported by the electronic latching speed.
The door can be passed through manually. We recommend
the Push & Go function.
3.3 Low energy product
The IS 9100 can be adjusted so that the requirements
of a low energy application (low energy drive unit) are in
accordance with the EN 16005 or DIN 18650, ANSI 156.19
and BS 7036-4. During the commissioning, the drive
parameters must be adjusted according to the specifications
of the respective standard.
The required safety of the system will be achieved with the
following characteristics:
• Reduced dynamic door panel forces/contact forces
• Low speeds
• Reduced static door panel forces/contact forces
• Force limitation
Due to system tolerances, the actual forces on the door
panel have to be measured after the teach-in run and
adjusted, if necessary, in order to comply with the local
standards and regulations.
Additional safety sensors to safeguard the rotational
movement are not required but optional if this becomes
necessary due to a risk assessment to be carried out
individually.
The safeguarding of the secondary closing edge must be
considered separately.
3.4 Control elements
The drive unit IS 9100 is electromechanical drives. The
interaction between motor gear unit and control unit makes
the automatic opening and closing possible in the first place.
The control unit must know certain parameters of the door in
order to achieve the ideal behavior.
The control unit is equipped with a user interface featuring 4
pushbuttons and a 2 digit display. This allows you to make
all settings specified in the parameter list.
During the commissioning, the key functions and the display
are configured so that - independent of the installation
direction of the pushbuttons - always the same functions and
the numbers and digits are correctly shown. The legend of
the pushbuttons can be removed and turned.
< 3s Quit
> 3s Reset
< 3s
> 3s
LEARN
> 8s
Fact-Setup
> 3s
PRG
DIN L
< 3s Quit
> 3s Reset
< 3s
> 3s
LEARN
> 8s
Fact-Setup
> 3s
PRG
DIN R
By pressing the pushbuttons, you can execute the following
functions:
Lower
pushbutton
• Setting of the installation direction following a mains
reset
• Browsing in parameter and error messages
• Reducing the parameter value
• Opening pulse
• Teach-in run
• Reset with factory setting (Fact-Setup)
Upper
pushbutton
• Browsing in parameter and error messages
• Increasing the parameter value
Right
pushbutton
• Open parameter menu
• Change selected parameter
• Save changed value
Left
pushbutton
• Cancel parameter change
• Exit parameter menu
Left and right pushbutton simultanuously
• Error acknowledgement
• Reset