59
Range
- 0,01....10,00 [s]
Default
value
- 2,00 [s]
Comments
- This value along with declared Number of transmission retries
to gas meter influences max. time of single data packet
transmission.
8.2.5.7.9. Number of devices
Function
- Defines number of declared register spaces (devices) read on
PORT2 from peripheral devices operating on M-Bus protocol.
Data type
- number
Range
- 1....16
Default
value
- 1
Comments
- n/a
8.2.5.7.10. MC
The table defining consecutive data blocks read from peripheral devices attached to
PORT2 operating in M-Bus protocol. The table can hold from 1 to 16 independent
blocks in one or more devices.
8.2.5.7.10.1. Address 1....16
Function
- Defines address of heat meter whose internal parameters shall
be read.
Data type
- number
Range
- 0....255
Default
value
- 0
Comments
- address 255 means querying stopped
.
8.2.5.7.10.2. Geographical coordinates format
Function
- Defines format of geographical coordinates received in NMEA
0183 protocol when writing into registers.
Data type
- selection list
Range
-
Degrees.minutes (DDMM.mmmmm)
Position registered in format
Degrees (DD.ddddddd)
Position registered in format
Default
value
Degrees.minutes (SSMM.mmmmm)
Comments
- n/a
8.2.5.7.10.3. Identifier 1....16
Function
- Defines additional number of heat meter whose internal
parameters shall be read.
Data type
- number