67
Range
- 0,00....163,83 [s]
Default
value
- 0,1 [s]
Comments
- Setting value appropriate to contact characteristics eliminates
disturbance caused by contact bounce thus preventing multiple
registration of what is in reality one pulse.
8.2.6.2.2.2.2. Analogue inputs
Function
- Defines time of measuring frequency of input signal in order to
convert it to analogue value.
Data type
- number
Range
- 0....255 [x 0,1 s]
Default
value
- 0
Comments
- for
0
(
zero
) value filtering is off.
Setting high time value influences stabilizing of result after
signal value change, but allows better precision of measuring
noisy signal.
8.2.6.2.2.2.2.1. Engineering units
Function
- Defines a name for engineering units
Data type
- text
Range
- letters and numerals, max 16 characters
Default
value
- x
Comments
- inserted text does not have any influence on the value of
measured analogue signal
8.2.6.2.2.2.2.2. Low reference - internal units
Function
- used along with other reference parameters for rescaling input
signal range to engineering units range.
Data type
- number
Range
- 0....65535
Default
value
- 0
Comments
- low reference point for internal units
8.2.6.2.2.2.2.3. Low reference - engineering units
Function
- used along with other reference parameters for rescaling input
signal range to engineering units range.
Data type
- number
Range
- 0....65535
Default
value
- 400
Comments
- low reference point for engineering units