TECHNICAL DATA
30
iV-Light ventilation unit | Installation instructions
5
Technical data
5.1
General specifications
Feature
Value
Operating range [°C]
-20 – 50
Extract air/outdoor air
Free from aggressive gases, dust
and oils
Flow rate in reversed mode [m³/h]
5 – 21
Extract airflow [m³/h] (EN 13141-8)
10 – 42
Sound pressure level, distance 2 m [dB (A)]
14 – 36
Standard sound level difference [dB]
34 – 47
Thermal efficiency of heat recovery (η'w)
0.84
Input voltage [V DC]
6 – 16
Power consumption [W]
1 – 3
Specific fan power input [W/(m³/h)]
0.2
Protection class (EN 61140)
III
Type of protection (EN 60529)
IP20
Standard filter filter class
ISO 16890
EN 779:2012
ISO Coarse 60 %
G4
Sensitivity of the air flow at ± 20 Pa (EN 13141-8)
S3
Electrical protection area
(in accordance with VDE 0100)
Outside protection areas 0 – 2
Frost protection
Automatic by reversing operation
(down to -20 °C)
Conformity