The assembly of the external termination variants is not part of this documentation!
It can be found in the installation instructions for the respective external termination.
23
INSTALLATION AND ASSEMBLY
23
iV-Light ventilation unit | Installation instructions
4.5 Installing the ventilation unit's external terminal
NOTICE
Installation on unfinished exterior walls leads to damage to the external termination!
•
Only install the external termination once the exterior wall is finished and has fully dried.
NOTICE
Penetration of condensation water and/or algae accumulation around the external termination
leads to damage to the masonry/exterior wall and/or discolouration of the façade!
• Secure sealing tape all the way around the weather protection grille before installing the
external terminal.
• Attach end-stop tape on the exterior wall side in the top half of the wall sleeve.
• Before installation, carry out a biocidal pre-treatment/water-repellent pre-treatment of the sur-
face around the external termination (consult your planner regarding this!).
Spirit level, cordless screwdriver, permanently elastic external sealant, sealing tape,
screws, scissors
Requirements:
• The exterior wall is completed and even.
• The wall sleeve is installed.
►
Remove the styrofoam discs from the wall sleeve
on the exterior wall side.
►
Shorten the end-stop tape to 210 mm.
►
Attach the shortened end-stop tape, 210 x 15 mm,
on the exterior wall side exclusively in the upper
area of the wall sleeve.
Both ends of the end-stop tape are located
above the horizontal central axis, so that
the fixing claws on the weather protection
grille are able to hook into the wall sleeve
on the left and right.
210 mm
!
Summary of Contents for 1001-0200
Page 1: ...www inventer de Installation instructions iV Light ...
Page 37: ...37 WARRANTY AND GUARANTEE 37 iV Light ventilation unit Installation instructions NOTES ...
Page 38: ...38 WARRANTY AND GUARANTEE 38 iV Light ventilation unit Installation instructions NOTES ...
Page 39: ...39 WARRANTY AND GUARANTEE 39 iV Light ventilation unit Installation instructions NOTES ...