5.  Remote configuration 

 
In  this  section  is  shown  how  the  IntesisBox

®

  can  be  configured  using  the  Intesis 

Configuration Software.  
 
For a more detailed explanation see the documentation of Intesis Configuration Software. 
 
 

5.1  Reception profiles 

 
Reception channels where up to 5 devices can be linked (see exceptions in Table 4.5). The 
links can be also achieved using the manual learning procedure (section 4.3). 
 
 

 

 

Figure 5.1 

Reception profiles with their associated signals and devices 

 
 

5.2  Transmission profiles 

 
Transmission  channels  to  be  used  to  teach  the  IntesisBox

®

  into  other  devices.  As  in  the 

reception  channels,  the  procedure  can  be  done  manually  just  following  the  steps  of  the 
teach-in procedure (section 4.2.2).  
 
 

Summary of Contents for PA-AC-ENO-1i

Page 1: ...IntesisBox PA AC ENO 1i PA AC ENO 1iC EnOcean Interface for PANASONIC Air Conditioners Compatible with Etherea Line User s Manual r1 eng Issue Date 02 2012...

Page 2: ...urnished under a license agreement or nondisclosure agreement The software may be used only in accordance with the terms of those agreements No part of this publication may be reproduced stored in a r...

Page 3: ...URL Email tel http www intesis com info intesis com 34 938047134 3 43 Interface for integration of Panasonic air conditioners into EnOcean systems Compatible with Etherea line air conditioners commer...

Page 4: ...linked to one profile 18 4 4 3 Return to factory settings 19 4 5 Remote management disablement 19 5 Remote configuration 20 5 1 Reception profiles 20 5 2 Transmission profiles 20 5 3 Configuration 21...

Page 5: ...intesis com info intesis com 34 938047134 5 43 8 8 Protect the IntesisBox from undesired remote access 30 8 9 Improve radio coverage of IntesisBox 30 9 Technical data and dimensions 31 10 Dimensions...

Page 6: ...y bi directionally all the functioning parameters of Panasonic air conditioners from EnOcean installations Small dimensions Quick installation and possibility of hidden installation External power not...

Page 7: ...ure 1 1 Typical application of IntesisBox in a hotel Typical transmitting EnOcean devices Thermostat Switches Key card Window contact Occupancy sensor Typical receiving EnOcean devices Actuators Gatew...

Page 8: ...be finished section 3 4 3 Configure the IntesisBox a Manually section 4 1 b Remotely using the Intesis Configuration Software section 5 3 4 Learn the EnOcean sensors gateways that will control the Int...

Page 9: ...nstalled in the largest uncovered part to the socket CN CNT of the AC unit s electronic circuit Close the AC indoor unit s front cover again Figure 3 1 IntesisBox connection diagram Important Do not m...

Page 10: ...emitted by the IntesisBox or by any other EnOcean device is determined by the room geometry and where they are placed As an example long narrow corridors with wide walls are an adverse situation Peop...

Page 11: ...ution with a repeater The situation of one of the receivers does not allow it to receive the transceiver telegrams To solve this situation the use of a repeater outside the screening zone Figure 3 4b...

Page 12: ...rs In case of a poor radio reception it may be helpful to use a repeater EnOcean repeaters do not require any configuration only a line power supply is needed A poor radio signal is received refreshed...

Page 13: ...C connector K2 Inputs connector K9 Bootloader connector L1 EnOcean LED L2 AC LED 4 Manual configuration 4 1 Configuration The IntesisBox Figure 4 1 has two sets of switches a push button and a rotary...

Page 14: ...ected it is possible to set the device to monitor mode and perform the teach in procedure These operations will not interfere in the normal behaviour of the device 4 2 1 Monitor mode Due to the transm...

Page 15: ...sent periodically according to the IntesisBox configuration section 5 3 1 Table 4 4 shows which signals and EEPs correspond to each Tx profile Profile Index Tx S2 Transmission signals EEP EnOcean Pro...

Page 16: ...ows the IntesisBox to be controlled by other EnOcean devices The IntesisBox has 14 reception Rx profiles Each Rx profile is assigned to a control signal of the AC unit Up to 5 devices can be linked to...

Page 17: ...le The L1 turns OFF when that happens 5 Once the learning procedure is finished set both S4 1 and S4 2 to OFF for a normal operation of the device Once that is done L1 turns OFF In section 14 can be f...

Page 18: ...2 to ON L1 will turn into flashing 100 ms on and 100 ms off 2 Set the profile selector S2 to the desired Rx profile Table 4 5 where the device to be deleted is saved 3 Push the Teach in button of the...

Page 19: ...2 to ON L1 will turn into flashing 100 ms on and 100ms off 2 Press the button S3 for 10 seconds After the first 5 seconds L1 will turn on during 1 second indicating that all the devices in the curren...

Page 20: ...on Software For a more detailed explanation see the documentation of Intesis Configuration Software 5 1 Reception profiles Reception channels where up to 5 devices can be linked see exceptions in Tabl...

Page 21: ...ark of Intesis Software SL URL Email tel http www intesis com info intesis com 34 938047134 21 43 Figure 5 2 Transmission channels with their EEPs and unique IDs 5 3 Configuration Using the Intesis Co...

Page 22: ...gured Threshold ambient temperature heat temperature under which the AC unit will be set to cool mode when AUTOCHANGEOVER is configured Min setpoint cool minimum setpoint allowed when AC unit is in co...

Page 23: ...cupancy 2nd action occupancy action type APPLY_DELTA it will apply an increment of temperature depending on the mode SWITCH_OFF the AC unit will be switched OFF Occupancy 2nd action delta heat if acti...

Page 24: ...Threshold ambient temperature cool 26 C Threshold ambient temperature heat 21 C Min setpoint cool 24 C Max setpoint cool 28 C Min setpoint heat 19 C Max setpoint heat 23 C Wake up time 120 seconds Wi...

Page 25: ...is sending a window opened message for a certain period of time default value 1 minute If the AC indoor unit is set to ON either by an EnOcean device or by the remote control the IntesisBox will set...

Page 26: ...uld be lost if there is a power down in the system Therefore it would be needed to set the previous state by actuating the key card 6 4 Occupancy sensors The IntesisBox has the functionality to automa...

Page 27: ...IntesisBox is in Learning mode in profile E or F 3 devices positions would be taken implying that only 1 device using MultiTeach in would be able to be fully linked in each profile If tried again wit...

Page 28: ...us LED L2 state ON OFF Period Meaning Turning on Pulse ON during 5 seconds Initialization process after start up or reset During normal operation Flashing 100ms ON 1900ms OFF Normal Operation During n...

Page 29: ...nked See an example of how an Intesis thermostat IS TK04PST will behave depending on the way it is linked If an IS TK04PST is linked to the Rx profile 0 On Off it will only be possible to turn on or o...

Page 30: ...arameters The IntesisBox parameters can be configured using the Intesis Configuration Software section 5 3 8 7 Check if the devices have been correctly learnt a Using the Intesis Configuration Softwar...

Page 31: ...inputs 4 x Potential free binary inputs dry contacts Signal cable length 5m unshielded may be extended up to 20m with twisted Compliant with the following standards IEC61000 4 2 level 4 15kV air disch...

Page 32: ...rk of Intesis Software SL URL Email tel http www intesis com info intesis com 34 938047134 32 43 10 Dimensions Figure 10 1 IntesisBox dimensions in mm 11 AC Unit Types compatibility A list of Panasoni...

Page 33: ...peed sensors and on off EEP for Generic HVAC interface Functions Mode vane position fan speed sensors and on off With this EEP plus the already existing EEP 07 10 03 and 07 20 11 all the information o...

Page 34: ...Vane Up Down position 0 Auto 1 Position 1 2 Position 2 3 Position 3 4 Position 4 5 Position 5 6 Not supported 7 10 Reserved 11 14 Not supported 15 N A DB_2 3 DB_2 0 Fan Speed 0 Auto 1 Low 2 Mid1 3 Mid...

Page 35: ...ed 255 N A 2 DB_2 7 DB_2 4 Vane Up Down position 0 Auto 1 Position 1 2 Position 2 3 Position 3 4 Position 4 5 Position 5 6 Not supported 7 10 Reserved 11 14 Not supported 15 N A DB_2 3 DB_2 0 Fan Spee...

Page 36: ...07 10 03 and 07 20 10 all the information of AC indoor unit can be sent and received allowing a much easier and complete control of these units Teach In The teach in telegram has the same structure as...

Page 37: ...Enable Remote controller 0b1 Disable Remote controller DB_0 1 Window contact 0b0 Windows opened 0b1 Windows closed DB_0 0 Not used Transmit mode Commands sent by the HVAC interface DB_3 Error code HI...

Page 38: ...See EnOcean Equipment Profiles EEP v2 1 and use the following structure DB_3 7 DB_3 2 Function same as teach in telegram heating valve 20 DB_3 2 DB_2 3 Type same as teach in telegram actuator 11 DB_2...

Page 39: ...an motor lead wire and connector Fan motor lock or block 8227 H23 Indoor heat exchanger temperature sensor abnormality Continuous for 5s Indoor heat exchanger temperature sensor open or short circuit...

Page 40: ...ir filter dirty Air circulation short circuit 12305 F11 4 way valve switching abnormality 4 times happen within 30 minutes 4 way valve switching abnormal 4 way valve Lead wire and connector 12311 F17...

Page 41: ...02 xx 05 03 xx 06 00 01 07 30 02 7 05 04 01 8 07 07 01 07 08 01 07 08 02 9 05 02 xx 05 03 xx A 05 02 xx 05 03 xx B 07 02 05 07 02 06 07 10 01 07 10 02 07 10 03 07 10 04 07 10 05 07 10 06 07 10 07 07...

Page 42: ...Point and Occupancy Control 07 10 06 Temperature Sensor Set Point and Day Night Control 07 10 07 Temperature Sensor Fan Speed Control 07 10 08 Temperature Sensor Fan Speed and Occupancy Control 07 10...

Page 43: ...peration is valid for all EU countries as well as for Switzerland Standards UNE EN 50491 3 2010 UNE EN 60950 1 2007 UNE EN 61000 6 2 2006 UNE EN 61000 6 3 2007 FCC ID SZV STM300C IC 5731A STM300C The...