35 / 43
EEP: 07-20-10 (CONTINUATION)
Transmit mode:
Commands sent by the HVAC interface
DB_3
Mode
1
0
Auto
1
Heat
3
Cool
9
Fan only
14
Dehumidification (dry)
15 ... 32
Not supported
33
… 254
Reserved
255
N/A
2
DB_2.7 ... DB_2.4
Vane Up/Down position 0
Auto
1
Position 1
2
Position 2
3
Position 3
4
Position 4
5
Position 5
6
Not supported
7 ... 10
Reserved
11 ... 14
Not supported
15
N/A
DB_2.3 ... DB_2.0
Fan Speed
0
Auto
1
Low
2
Mid1
3
Mid2
4
Mid3
5
High
6 ... 14
Not supported
15
N/A
DB_1
Not used
DB_0.3
Learn Button
0b0
Teach-in telegram
0b1
Data telegram
DB_0.2 ... DB_0.1
Room occupancy
00:
Occupied
01:
StandBy (waiting to perform action)
10:
Unoccupied (action performed)
11:
Off (no occupancy and no action)
DB_0.0
On/Off
0b0
Off
0b1
On
1
Other modes don’t apply to this AC interface. It will only send this ones
2
N/A: it is send when the value of the parameter is not known