International comfort products DLCBHR Installation Instructions Manual Download Page 23

23

INSTALLATION OF THE CONDENSATE PIPE

1. The condensate pipe should keep a inclination angle of 5 ~

10”, to facilitate the drainage of the condensate water. And

the joints of the condensate pipe should be insulated by the
insulation material to prevent condensing (see Fig. 36).

Insulating Layer for the Condensate Pipe

Pipe Lid

Fig. 36

-

Thermal Insulation of the Condensate Pipe

2. There is a condensate outlet on both the left and right sides of

the unit. Once one is confirmed for use, the other should be

clogged by a rubber plug, bundled by the binding wire and
insulated by the insulation material to avoid water leakage.

3. The right outlet is defaulted to be clogged with a plug.

IMPORTANT

: No water leakage is allowed on the joint of the

condensate pipe.

DESIGN OF THE DRAIN PIPE

1. The drain pipe should always be kept an inclination angle

(1/50~1/100) to avoid water from gathering.

2. During the connection of the drain pipe and device, do not

impose excessive force on the pipe on one side of the device.

Additionally the pipe should be secured closely to the device.

3. The drain pipe can be the ordinary hard PVC pipe which

can be purchased locally. During the connection, inset the

end of the PVC pipe to the drain outlet, then tighten it with
the drain hose and binding wire. Never connect the drain

outlet and the drain hose with adhesive.

4. When the drain pipe is used for multiple devices, the public

section of the pipe should be 4 in (100 mm) lower than the

drain hole of each device and it is better to use the much
thicker pipe for such a purpose.

INSTALLATION OF THE DRAIN PIPE

1. The diameter of the drain pipe should be larger than or

equal to that of the refrigerant pipe (PVC pipe, outer
dimater: 1 in (25 mm), wall thickness

0.06 in (1.5 mm).

2. The drain pipe should be a short as possible and with at

least a 1/100 degree of slope to avoid forming air pockets.

3. If the proper degree of slope of the drain pipe is not

allowed, a lift pipe should be installed.

4. A distance of 3.28 ft~4.92 ft (1m~1.5 m) should be kept

between the hangers to avoid the drain hose from making a
turn.

3.28 ft~4.92 ft 

(1m~1.5 m)

(Wrong) 

Fig. 37

-

Slope Degree

5. Insert the drain hose into the drain hole and tighten it with

clamps.

6. Wrap the clamps with large amount of sponge for thermal

insulation.

7. The drain hose inside the room also should be insulated.

Clamp (accessory)

Sponge (gray)

Drain Hose

Sponge (accessory)

Clamp
(accessory)

Max. 4mm

Fig. 38

-

Drain Hose Insulation

PRECAUTIONS FOR THE LIFT PIPE

The lift pipe install height should be less than 33 1/2 in (850 mm). We
recommend setting an inclination angle 1~ 2

_

for the lift pipe toward

the drainage direction. If the lift pipe and the unit form a right angle,
the height of the lift pipe must be less than 31 1/2 in (800 mm).

 1°

1~1.5m

1000mm

850mm

11 4/5 in (300 mm)

150mm

Ceiling

Clamp (accessory)

Drain Hose (accessory)

Lift Pipe

Hanger Bracket

Fig. 39

-

Installation Height

NOTE

:

1. The inclination height of the drain hose should be within 3

in. (75 mm) so that the outlet of the drain hose does not

suffer any external force.

2. If multiple drain pipes converge, follow the installation

steps below.

The specification of the joint of the drain pipe should be suitable to the running capacity of the unit 

Drain Hose (accessory)

Max.75mm

Max.1000mm

Fig. 40

-

Multiple Line Convergence

Summary of Contents for DLCBHR

Page 1: ...SIDERATIONS 2 GENERAL 2 SYSTEM REQUIREMENTS 3 4 ELECTRICAL DATA 4 PARTS LIST 6 DIMENSIONS 7 14 CLEARANCES 15 17 DIMENSIONS BRANCH BOXES 18 19 INSTALLATION GUIDE 20 HIGH WALL INDOOR UNIT INSTALLATION 2...

Page 2: ...ese words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal...

Page 3: ...Size Suction In 1 2 1 2 5 8 5 8 Table 4 Indoor Cassette Indoor Cassette Size 12 18 24 Pipe Connection Size Liquid In 1 4 1 4 3 8 Pipe Connection Size Suction In 3 8 1 2 5 8 Table 5 Indoor Ducted Indoo...

Page 4: ...OOR FAN VOLT PHASE HZ MAX MIN V PH HZ FLA HP W 9 208 230 1 60 253 187 208 230 1 60 0 28 1 24 80 12 0 31 1 18 80 18 0 41 1 12 100 21 0 5 1 36 124 24 0 5 1 36 124 Table 12 Floor Console UNIT SIZE System...

Page 5: ...ion Method for Power and Communication Wiring To minimize communication wiring interference Power Wiring The main power is supplied to the outdoor unit The field supplied power wiring from the outdoor...

Page 6: ...control 1 Battery 1 5V 2 GasketM6X 18X1 4 4 GasketM10X 30X2 5 10 Screw ST4 8X13 HC 4 Screw M6X25 4 Nut of Connector Pipe B Package 1 Pipe Connection Nut I shape 1 Connection wire of wired control 1 Wi...

Page 7: ...Table 14 High Wall DLFAHH Dimensions Unit Size W In mm D In mm H In mm Q In mm Operating Weight Lbs kg 9k 37 8 960 g 8 07 205 12 6 320 2 16 55 33 07 15 12k 37 8 960 8 07 205 12 6 320 2 16 55 33 07 15...

Page 8: ...OOR CONTINUED Fig 3 Wall Dimensions Table 15 High Wall DLFBHB Unit Size W In mm D In mm H In mm Operating Weight 9k 34 09 8 23 11 5 24 3 12k 34 09 8 23 11 5 24 3 18k 40 079 9 055 12 6 30 9 24 46 378 1...

Page 9: ...9 DIMENSIONS INDOOR CONTINUED Fig 4 Cassette Grill Dimensions Fig 5 Cassette Side View Dimensions...

Page 10: ...10 DIMENSIONS INDOOR CONTINUED Fig 6 Cassette Connection Side View Dimensions Fig 7 Cassette Top View Dimensions...

Page 11: ...in 615 mm 30 4 5 in 782 mm 6 1 7 in 156 mm 7 7 8 in 200 mm 25 in 635 mm 12 18 37 in 942 mm 19 1 3 in 491 mm 34 in 862 mm 32 2 7 in 820 mm 35 3 7 in 900 mm 24 1 5 in 615 mm 38 2 3 in 982 mm 6 1 7 in 15...

Page 12: ...12 DIMENSIONS INDOOR CONTINUED Fig 9 Floor Console Dimensions...

Page 13: ...13 DIMENSIONS OUTDOOR Fig 10 Outdoor Dimensions Size 18 Fig 11 Outdoor Dimensions Size 24...

Page 14: ...14 DIMENSIONS OUTDOOR CONTINUED Fig 12 Outdoor Dimensions Size 30 42 Fig 13 Outdoor Dimensions Size 48 56...

Page 15: ...15 CLEARANCES INDOOR 6 0 15m min 5 0 13m min 6 5 0 13m min 1 8m CEILING FLOOR Fig 14 High Wall Clearance Fig 15 Cassette Clearance...

Page 16: ...16 CLEARANCES INDOOR CONTINUED Fig 16 Ducted clearance Fig 17 Floor console clearance...

Page 17: ...ES OUTDOOR CONTINUED A D B Air outlet Air inlet C E Fig 18 Clearances Outdoor 18 42 Table 17 Clearances Outdoor UNIT Minimum Value in mm A 24 609 B 24 609 C 24 609 D 4 101 E 4 101 Fig 19 Clearances Ou...

Page 18: ...26 mm 3 4 7 in 91 mm 3 1 7 in 80 mm 2 2 5 in 61 mm 3 1 2 in 88 mm 7 1 6 in 182 mm 3 1 3 in 85 mm 2 1 2 in 64 mm Fig 20 Outline Dimensions Table 18 Outline Dimensions Sorts Indoor unit side inch mm Out...

Page 19: ...1 2 in 64 mm 13 8in 35mm 23 4in 70mm 23 4in 70mm 1 4 5in 35mm 23 4in 70mm 23 4in 70mm Fig 22 Outline Dimensions Table 20 Outline Dimensions Sorts Indoor unit side inch mm Outdoor unit side inch mm Po...

Page 20: ...WALL FOR INTERCONNECTING PIPING DRAIN AND WIRING Refrigerant Line Routing The refrigerant lines may be routed in any of the four directions shown in Fig 24 a and b For maximum serviceability it is re...

Page 21: ...shown in Fig 28 48mm Fig 28 Install the indoor unit S Prior to the installation make a good preparation for all piping refrigerant pipe drain pipe and wiring wires of the wired controller wires betwee...

Page 22: ...r Supply Outlet Return Air Inlet Size A B C D 09 6 1 7 in 156 mm 26 in 662 mm 22 5 6 in 580 mm 22 5 6 in 580 mm 12 18 6 1 7 in 156 mm 34 in 862 mm 30 5 7 in 780 mm 6 3 8 in 162 mm 21 6 1 7 in 156 mm 4...

Page 23: ...ose INSTALLATION OF THE DRAIN PIPE 1 The diameter of the drain pipe should be larger than or equal to that of the refrigerant pipe PVC pipe outer dimater 1 in 25 mm wall thickness 0 06 in 1 5 mm 2 The...

Page 24: ...ll in areas with or near an abundance of oil S Do not install in areas with an acid base area S Do not install in areas with an irregular electrical supply Indoor Unit Installation Drawings The indoor...

Page 25: ...e 2 Insert a wall pipe into the hole 3 Insert a wall cover into wall pipe Inside Outside Caulking Wall embedded pipe field supply Wall hole cover Wall embedded pipe field supply 2 1 6 in 55 mm Fig 48...

Page 26: ...ide casings 2 Upper casing 3 Side casings Remove the pillar Remove 7 screws Fig 51 Remove the screws For Side Piping S Remove the pillars 1 Remove the 7 screws 2 Remove the upper casing 2 tabs 3 Remov...

Page 27: ...downward so that the chips do not enter the pipe 3 Fit the flare nut on the pipe 4 Flare the pipe 5 Check that the flaring is properly made 1 DO not use mineral oil on flared part 2 Prevent mineral oi...

Page 28: ...and water pump in the dining room and kitchen which would reduce the capacity of heat exchanger lead water leakage and abnormal operation of the water pump The following treatment should be taken und...

Page 29: ...motor oil screw it by hand and then tighten with a spanner Refer to form 1 to check if the wrench had been tightened too tight would mangle the nut and lead leakage Examine the connection pipe to see...

Page 30: ...the impact fastener after the connection 2 Entwine the small sponge on the electric wire entwine to prevent condensation 3 Impact tightly with an impact fastener after connection Then fir on the elec...

Page 31: ...pen service valves or remove protective caps from tubing ends until all the connections are made S Bend tubing with bending tools to avoid kinks and flat spots S Keep the tubing free of dirt sand mois...

Page 32: ...on sizes 48 and 56 Separate power connection is required for the Outdoor unit and the Branch Boxes Refer to Branch Box installation instructions NOTE CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow...

Page 33: ...es and nine different types of indoor units high wall cassette ducted and floor console At least one Branch Box KSAUI0201AAA up to 2 indoor units or KSAUI0401AAA up to 3 indoor units is required on th...

Page 34: ...34 CONNECTION DIAGRAMS 18 42 Fig 75 Connection Diagram Sizes 18 42 48 56 Fig 76 Connection Diagram Sizes 48 56 Connection Diagram Fig 77 Connection Diagram Branch Box...

Page 35: ...0 for each indoor unit SYSTEM VACUUM AND CHARGE UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Never use the system compressor as a vacuum pump...

Page 36: ...inue operating for an additional 15 minutes 2 Close service valves and shut off vacuum pump 3 Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig 4 Close servi...

Page 37: ...through which the cables and tubing pass INDOOR UNIT 1 Do all Remote Control buttons function properly 2 Do the display panel lights work properly 3 Does the air deflection louver function properly 4...

Page 38: ...ugh remote controller within 200s displayed directly on nixie tube after 200s P8 Refrigerant lacking or blockage protection of system not available for residential ODU F0 Charging malfunction of capac...

Page 39: ...tdoor ambient sensor malfunction Flash 6 times F3 Outdoor tube sensor malfunction Flash 5 times F4 Exhaust sensor malfunction Flash 7 times F5 Attain the temperature of switch on Flash 8 times Frequen...

Page 40: ...ent protection Flash 21 times L9 L9 Compressor overload protection Flash 22 times H3 H3 Compressor discharge temperature protection Flash 23 times E4 E4 Lack of refrigerant or jam protection Flash 31...

Page 41: ...12 times Indoor unit 9 is connected Flash 13 times Indoor anti freeze protection E2 E2 Inside temperature sensor error F1 F1 Evaporator midway temp sensor error F2 F2 Liquid pipe of BU module tempera...

Page 42: ...rature sensor error Flash 2 times b5 b5 indoor unit address Indoor unit B gas tube temperature sensor error Flash 3 times b7 b7 indoor unit address Indoor unit B liquid tube temperature sensor error F...

Reviews: