Power cable size and length requirements
Using the proper gauge of power cable will ensure proper operation and avoid voltage drops. See
Table 4
for
the recommended cable gauge for varying maximum cable lengths and power draws.
Table 4.
Recommended power cable gauges based on maximum lengths for an operating voltage of 24 VAC (±4 VAC)
Wire gauge
Domes with fan (20 VA)
Domes with
12 W heater/fan (x2) (45 VA)
HD domes with
23 W heater/fan (x2) (66 VA)
AWG
mm
(dia.)
feet
meters
feet
meters
feet
meters
10
2.60
1569
478
784
238
490
149
12
2.05
988
301
494
150
309
94
14
1.62
620
188
310
94
194
59
16
1.29
391
119
196
59
122
37
18
1.02
246
74
123
37
77
23
WARNING:
Be aware that the power requirements for UltraView PTZ are different, which may require new cabling
when replacing CyberDomes with UltraView PTZ domes.