MGC2 – UserManual
PolyGard
®
is a registered trademark of MSR-Electronic GmbH
4.8.6 Average Function
Not used in USA.
The each active sensor point the Gas Controller calculates the arithmetic average value out of 10
measurements got within the time unit defined in the menu „AV-time“. Depending on the definition of the operating
mode the alarm is evaluated with the current or the average value. In the average mode, the average value is
indicated in the menu “Sensor Values” next to the current value. The control mode (current or average value) for the
evaluation of the alarm is defined for each sensor point.
The alarm evaluation of the control mode “Average Value” is overlaid by the current value, when the current value
exceeds the alarm threshold defined in the menu “AV-Overlay”. The overlay is delayed by the time factor defined in this
menu. The average overlay function is only active for the gas type CO.
Symbol
Description Default
Status
Function
120 s
120 ppm
AV Overlay
120 s
120 ppm
sec. = Delay time of average value overlay. 0 = No overlay function
ppm = Threshold average overlay
1800 s
AV Time
1800 s
sec. = Time for calculating the average value
4.8.7 System Time, System Date
Input and correction of time and date. Selection of time and date format.
Symbol
Description Default
Status
Function
US
Time Format US
US = Display of time and date in US format
EU = Display of time and date in EU format
hh.mm.ss
Time
hh.mm.ss pm = Input of the correct time (US format)
hh.mm.ss = Input of the correct time (EU format)
MM.DD.YY. Date
MM.DD.YY = Input of the correct date (US format)
TT.MM.JJ = Input of the correct date (EU format)
4.8.8 Service Password (Maintenance)
Change of the system password for maintenance. With this password you can set the maintenance date anew and
acknowledge the fault message.
Symbol
Description Default
Status
Function
1
Service
Password
1
**** = Define the individual password with 4 characters
(maintenance)
4.8.9 GC Address
This configurable functionality is available from version 9.02.
The option of an additional serial interface allows data to be transmitted to the superior systems without feedback. This
option cannot be retrofitted.
The description of the interface can be read from a separate document.
In this menu, the address of the gas controller can be set for this RS485 interface.
Symbol
Description Default
Status
Function
1
GC Address 1
0-255 = GC address