MGC2 – UserManual
PolyGard
®
is a registered trademark of MSR-Electronic GmbH
Alarm - 1 2 3 4 5
Fault - 1 2 3 4 5
Assign SP fault to alarm
See 4.6.9
A1 A2 A3 A4 A5
1 2 3 4 0
Assign alarm to alarm relay
See 4.6.10
Analog Output
0
Assign SP signal to analog output
See 4.6.11
C/A Mode
CV
Define control mode
See 4.6.8
OFF-Delay Time
0 s
Set delay time for alarm OFF
See 4.6.7
ON-Delay Time
0 s
Set delay time for alarm ON
See 4.6.7
Hysteresis
15 ppm
Hysteresis
See 4.6.6
4.6.1 Activate – Deactivate SP
Symbol
Description
Setting
Status
Function
SP01
Sensor point
Selection SP No. / analog transmitter
Active
SP Status
not active active
= Sensor point activated at the controller
not active = Sensor point not activated at the controller
4.6.2 Lock or Unlock SP
This functionality is available from version 9.02
If a transmitter is damaged or completely destroyed, the consequence is that the ventilation works continuously. This
functionality can be used until the transmitter is repaired or replaced.
In the Lock Mode the function of the existing transmitter is put out of service, which means there is no alarm or fault
message at this sensor point. If at least one transmitter is blocked in its functionality, the collective fault message is
activated, the yellow fault LED is flashing and there is a message in the menu System Errors.
Symbol
Description
Setting
Status
Function
SP01
Sensor point
Selection Lock Yes/No
No
No
No = SP free, normal operation
Yes = SP locked, SSM (collective error message) active