MGC2 – UserManual
PolyGard
®
is a registered trademark of MSR-Electronic GmbH
4.6 Menu SP Parameter
For reading and changing sensor point parameters for each bus and analog transmitter including registration of SP
and assignment of the alarm relays.
The presentation of the SP parameters depends on the system parameter settings for the GC mode (see 4.7.3).
Threshold 2
100 ppm
Define threshold 2
See 4.6.6
Threshold 3
120 ppm
Define threshold 3
See 4.6.6
Threshold 1
80 ppm
Define threshold 1
See 4.6.6
SP Signal
Linear
Adjust signal form of the transmitter
See 4.6.5
Measuring range
300 ppm
Definition measuring range
See 4.6.4
Gas unit. AF
CO
ppm
0
Definition of gas type, unit and number
of alarms at falling concentrations (AF)
See 4.6.3
Lock
No
Lock or unlock SP
See 4.6.2
SP Mode
active
Activate or deactivate SP
See 4.6.1
SP Parameter
(Main menu)
SP01
Active
(Selection SP No. – Parameter analog transmitter)
Threshold 5
120 ppm
Define threshold 5
See 4.6.6
Threshold 4
120 ppm
Define threshold 4
See 4.6.6