MGC2 – UserManual
PolyGard
®
is a registered trademark of MSR-Electronic GmbH
4.2 Status Alarm
Display of the actual alarms in plain text in the order of their arrival. Only those sensor points are displayed, where at
least one alarm is active. Changes are not possible in this menu.
SP02
A1 A2
Symbol
Description
Function
SP02
Sensor (SP) Point No.
AX
Status Alarm
A1 = Alarm 1 ON
A2 = Alarm 2 ON
A3 = Alarm 3 ON
A4 = Alarm 4 ON
A5 = Alarm 5 ON
4.3 Status Relay
Reading of the actual status of alarm relays, manual operation of the alarm relays.
R 01
OFF
Symbol
Description
Setting Status
Function
R 01
Relay No. 01
OFF
Status Relay
OFF
OFF
= Relay OFF (no gas alarm)
ON
= Relay ON (gas alarm)
Manual OFF
= Relay manual OFF
Manual ON
= Relay manual ON
Latching mode = Relay in latching mode
4.3.1 Manual Operation of the Relays
The manual operation of the alarm relays is managed in the menu “Status Relay” or externally via an assigned digital
input. In the manual ON or OFF status, the alarm LEDs at the Gas Controller are lit continuously.
The external operation of the alarm relay via an assigned digital input has priority to the manual operation in the menu
“Status Relay” and to gas alarm.
Relays manually operated in the menu “Status Relay” are canceled again by selection of the automatic function.
Acknowledging the relays in latching mode is also effected in this menu or by a digital input.
Manual OFF
Select the function:
Manual ON
= Relay ON
Manual OFF = Relay OFF
Automatic
= Cancel manual operation
Reset?
= Reset of a latching mode
Take over the function
Manual ON
Select the function manual operation
R 01
OFF
Select the relay
R 01
Manual OFF