15
Setup
CAUTION:
Protect the server from power fluctuations and temporary interruptions with
a regulating uninterruptible power supply (UPS). This device protects the hardware from
damage caused by power surges and voltage spikes and keeps the system in operation
during a power failure.
When installing more than one server, you may need to use additional power distribution
devices to safely provide power to all devices. Observe the following guidelines:
•
Balance the server power load between available AC supply branch circuits.
•
Do not allow the overall system AC current load to exceed 80 percent of the branch circuit
AC current rating.
•
Do not use common power outlet strips for this equipment.
•
Provide a separate electrical circuit for the server.
5.1.4 Electrical Grounding Requirements
The server must be grounded properly for optimal operation and safety. In the United
States, you must install the equipment in accordance with NFPA 70, 1999 Edition (National
Electric Code), Article 250, as well as any local and regional building codes.
In Canada, you must install the equipment in accordance with Canadian Standards
Association, CSA C22.1, and Canadian Electrical Code. In all other countries, you must
install the equipment in accordance with any regional or national electrical wiring codes,
such as the International Electrotechnical Commission (IEC) Code 364, parts 1 through 7.
Furthermore, you must be sure that all power distribution devices used in the installation,
such as branch wiring and receptacles, are listed or certified grounding-type devices.
Because of the high ground-leakage currents associated with multiple servers connected to
the same power source, Inspur recommends the use of a PDU that is either permanently
wired to the building’s branch circuit or includes a nondetachable cord that is wired to
an industrial-style plug. NEMA locking-style plugs or those complying with IEC 60309 are
considered suitable for this purpose. Using common power outlet strips for the server is not
recommended.
Summary of Contents for NF8480M5
Page 1: ...Inspur Server User Manual NF8480M5 ...
Page 66: ...60 information 3 2 Create RAID Volume Enter this menu interface as shown below ...
Page 92: ...86 sensor Figure 6 Sensor fru Figure 7 Fru chassis Figure 8 Chassis user Figure 9 User ...
Page 93: ...BMC Settings 87 mc Figure 10 MC fan Figure 11 Fan psu Figure 12 Psu id Figure 13 Id diagnose ...
Page 143: ...BMC Settings 137 Figure 56 SOL Setting in BIOS Figure 57 Default Serial Setting ...