Display
Fault Name
Possible Causes
Solutions
Err08
Control power
fault
The input voltage exceeds the allowed range.
Adjust the input voltage to within the allowed range.
Err09
Undervoltage
1. Instantaneous power failure occurs.
2. The input voltage exceeds the allowed range
3. The DC bus voltage is too low
☆
.
4. The rectifier bridge and buffer resistor are faulty.
5. The drive board is faulty.
6. The control board is faulty.
1: Reset the fault.
2: Adjust the input voltage to within the allowed range.
3 to 6: Seek for maintenance.
Err10
Drive overload
1. The load is too heavy or the rotor is locked.
2. The drive is of too small power class.
1: Reduce the load, or check the motor, or check the
machine whether it is locking the rotor.
2: Select a drive of higher power class.
Err11
Motor overload
1. F9-01 is too small.
2. The load is too heavy or the rotor is locked.
3. The drive is of too small power class.
1: Set F9-01 correctly.
2: Reduce the load, or check the motor, or check the
machine whether it is locking the rotor.
3: Select a drive of larger power class.
Err12
Power input
phase loss
1. The three-phase power supply is abnormal.
2. The drive board is faulty.
3. The lightening protection board is faulty.
4. The control board is faulty.
1: Check the power supply.
2 to 4: Seek for maintenance.
Err13
Power output
phase loss
1. The cable between drive and motor is faulty.
2. The drive's three-phase output is unbalanced
when the motor is running.
3. The drive board is faulty
4. The IGBT is faulty.
1: Check the cable.
2: Check the motor windings.
3 to 4: Seek for maintenance.
Err14
IGBT overheat
1. The ambient temperature is too high.
2. The air filter is blocked.
3. The cooling fan is damaged.
4. The thermal sensor of IGBT is damaged.
5.The IGBT is damaged.
1: Reduce the ambient temperature.
2: Clean the air filter.
3 to 5: Seek for maintenance.
Err15
External
equipment fault
1. External fault signal is input via DI.
2. External fault signal is input via VDI.
Reset the fault.
Err16
Communication
fault
1. The host computer is abnormal.
2. The communication cable is faulty.
3. The extension card type set in F0-28 is incorrect.
4. The communication parameters in group FD are
set improperly.
1: Check cabling of the host computer.
2: Check the communication cabling.
3: Set F0-28 correctly.
3: Set the communication parameters properly.
Err18
Current
detection fault
The drive board is faulty.
Replace the drive board.
Err19
Motor tuning
fault
1. Motor parameters are wrong.
2. Motor tuning overtime.
1. Check motor parameters F1-00 to F1-05.
2. Check the wiring between drive and motor.
Err21
EEPROM
read-write fault
The EEPROM chip is damaged.
Replace the main control board.
Err23
Short circuit to
ground
The motor is short-circuited to ground.
Replace the cables or motor.
Err26
Accumulative
running time
reached
The accumulative running time reaches the setting of
F8-17.
Clear the record by performing parameter initialization
(set FP-01 to 2).
Err27
User-defined
fault 1
1. The user-defined fault 1 signal is input via DI.
2. User-defined fault 1 signal is input via VDI.
Reset the fault.