ITC-106 User Manual
Inkbird Tech. Co., Ltd. www.ink-bird.com
8
6.23 Sensor Input Type Setting:
Set the sensor input type as required(the faulty is the "K" type), the temperature need to
calibrated for there will be deviation due to the sensor and the operating environment.
6.24 Output Parameters Setting:
The recommended control mode for the first use is the PID control(default settings of PID
control), please select the self-tuning mode when the controlling temperature cannot reach
the desired value after it worked over time with the stable controlled temperature.
Under the self-tuning mode, the temperature will exceed the set value and activate the
alarm. The exceeding temperature value is related to the heating system but it will return
to normal after finished the self-tuning. If the temperature control requirement is
undemanding, please select the ON/OFF control mode which its range of temperature
controlling is depended on the dF(hysteresis). As below is the setting and the calculation:
The low temperature point=SV setting value-dF
The high temperature point=SV setting value+dF.
※
dF(hysteresis) can be worked both on alarm setting and ON/OFF control mode.
6.25 PID Parameters Setting:
SSR control output: the control period(CtrL) can be set within 4 seconds(default 2
seconds);
Relay control output: The control period (CtrL) should be set to longer time(the normal is
18s) that would prolong the work life of the relay.
6.26 Setup Flow Chart:
(Please check next page)