2. Specification 

Supply Voltage 

 AC 100~240V 50/60Hz  (model:ITC-106RH, ITC-106VH) 

 AC/DC 12~24V  50/60Hz (model:ITC-106RL, ITC-106VL) 

 DC 12~24V  (model:ITC-106RL, ITC-106VL) 

Operating 

Voltage 

Range 

85~110% of the rated voltage 

Power Consumption 

5VA

100~240VAC

 

4VA

12~24VAC

 

3W

12~24VDC

 

Display Code 

PV: displays in red high luminance LED with 9.9mm height of 4 

digits 

SV: displays in green high luminance LED with 8.00mm height 

of 4 digits 

Display Accuracy 

±0.2%FS  0.1ºC/ ºF(

1000ºC/ ºF)

1ºC/ ºF(≥1000ºC/ ºF) 

Sampling Period 

 0.5 second 

Temperature 

Compensation 

 0~50 ºC /32~122ºF 

Control Output 

Relay Output: AC 250V 3A (resistive load) 

Voltage Output (for driving SSR): 12VDC, 30mA DC 

Maximum load: 600Ω 

Electrical Life of Relay:100,000 times 

Alarm Output 

Relay Output: AC 250V 3A (resistive load) 

Weight 

About 140g 

Working Temperature 

 -10~ 55 ºC / 14~ 131 ºF(No freeze or condensation) 

Working Humidity 

 RH 35-85% 

Storage Temperature 

 -25~65ºC / -13~ 149 ºF (No freeze or condensation) 

 

Models and Specification 

Model 

 Control Output 

Supply Voltage 

ITC-106RL 

Relay Output 

AC/DC 12~24V 

ITC-106VL 

SSR Output 

AC/DC 12~24V 

ITC-106RH 

Relay Output 

AC 100~240V 

ITC-106VH 

SSR Output 

AC 100~240V 

 

 

 

 

 

 

 

Summary of Contents for ITC-106

Page 1: ...prior written permission Disclaimer Inkbird has made every effort to ensure that the information contained in this document is accurate and complete however the contents of this document are subject...

Page 2: ...nel Instruction 6 6 Setting Parameters 7 6 1 Sensor Type and Measuring Range 7 6 2 Operation Guide 7 6 21 Boot screen display 7 6 22 Enter the settings menu 7 6 23 Sensor Input Type Setting 8 6 24 Out...

Page 3: ...ric shock fire or malfunction Do not use the product where subject to flammable or explosive gas Otherwise injury from explosion may occasionally occur Never disassemble modify or repair the product o...

Page 4: ...ccuracy 0 2 FS 0 1 C F 1000 C F 1 C F 1000 C F Sampling Period 0 5 second Temperature Compensation 0 50 C 32 122 F Control Output Relay Output AC 250V 3A resistive load Voltage Output for driving SSR...

Page 5: ...when there are two or more temperature controllers installed 4 Wiring Diagram 2 wires sensor 3 wires sensor Thermocouple Output Relay Output Voltage Power Connection 9 and 10 terminals are for power...

Page 6: ...rapidly by keeping press this button DOWN Button when setting the value pressing the down button can be decrease the value that would be reduced rapidly by keeping press this button SHIFT Button when...

Page 7: ...750 F E 0 1000 C 0 1800 F J 0 1000 C 0 1800 F B 0 1800 C 0 3200 F N 0 1000 C 0 1800 F Remarks The faulty input sensor is the K type If select the wrong input sensor the measuring temperature will be i...

Page 8: ...and activate the alarm The exceeding temperature value is related to the heating system but it will return to normal after finished the self tuning If the temperature control requirement is undemandin...

Page 9: ...ITC 106 User Manual Inkbird Tech Co Ltd www ink bird com 9...

Page 10: ...ndition by the original purchaser not transferable against defects caused by INKBIRD s workmanship or materials This warranty is limited to the repair or replacement at INKBIRD s discretion of all or...

Reviews: