62
Installation
Fire detection and extinguishing system
100Vrms supervised speaker output
In the case of a supervised line, this presents an additional tone of 20kHz, for impedance measurement.
The IAS-ADAPT module provides, by inserting a jumper (
paragraph 3.21 - [E]
,
paragraph 3.21 - [F]
), a filter to eliminate the
supervision tone from the audio output.
4.8.2Microphone bases connection
Cables:
Double shielded not crossed cat. 5E SF/UTP cable
4.9
IFAMAMP internal module wiring
This paragraph illustrates the wiring possibilities via the IFAMAMP module, necessary for the connection for speaker lines
driven with a maximum signal of 100 Vrms.
Note:
The sum of the power of all the speakers connected to the module must be less than or equal to 250W.
4.9.1 Audio output connection (LINE A/B)
Cables:
2 pole cable as per the reference standard
EN IEC 62368-1:
Touching uninsulated terminals or live wiring with bare hands can cause electric
shock.
Speaker outputs, single line connection
GND
70V 1V GND
100V
20KHz 1V
GND
FILTER
IAS-ADAPT1000
Jumper
inserted
100Vrms audio
output with
20kHz tone
A/B PAGERS
IFAMEVAC
BASE #1
BASE #2
BASE #64
LINE A/B
Ferrite
Speaker 1
Speaker n
Speaker 2