![INIM Previdia Ultra Installation Manual Download Page 30](http://html1.mh-extra.com/html/inim/previdia-ultra/previdia-ultra_installation-manual_2061402030.webp)
30
Description of the Previdia Ultra system parts
Fire detection and extinguishing system
3.8
IFM24160, internal power-supply module
The IFM24160 internal module supplies and distributes power through the CAN drive connection bar and through the
two outputs, OUT 1 and OUT 2.
In installations where several control panels are connected in a network, it is necessary to use an IFM24160 power-supply
module for each control panel.
In installations where the control panel comprises more than one cabinet, you can install a power supply in each cabinet.
The total voltage available equals the sum of the voltages of each power supply added together minus 1A for correct
cable balance.
FPMCPU comes with:
• battery connection wire with thermal probe
• battery to battery connection wire
• 3 screws for securing the module to the grounding bar
• wire with eyelet terminal for connection to earth
• 1 ferrite
• Instructions manual
Consumption @ 27.6V
stand-by
20mA
maximum
40mA
mains fault
30mA
Maximum voltage on OUT 1
1.5A @27.6V
Maximum voltage on OUT 2
1.5A @27.6V
Maximum voltage on RELAY
5A, 30V
[A]
Status LED
[H]
L N
AC Mains input terminals
[B]
Mini USB port
[I]
Hole for the Earth bar screw and for
the Earth conductor
[C]
Jumper connectors for enablement of the
ground-fault test
[J]
Hole for the grounding bar screw and for the wire
with the eyelet terminal
[D]
OUT1
Supervised output
[K]
230/
115 V
Input voltage selector
[E]
OUT 2
[L]
CAN DRIVE/CAN DRIVE+ connector (opposite)
[F]
RELAY
Relay - voltage free contact
[G]
Battery connector
IFAMPSU module - technical specifications
F
D
C
B
L
A
K
H
G
I
J
E