Installation manual
Installation
53
4.3
Mounting the front-plate modules
The front-plate modules (FPAMIAS, FPMCPU, FPMNUL, FPMLED, FPMLEDPRN, FPMEXT) can be mounted to one of the
apertures on the cabinet front plate (
paragraph 3.2 - [B]
). The FPMCPU module can also be mounted to front plate of the
PRREP repeater enclosure.
1.
Align the 6 holes on the module frame (
paragraph 3.4 - [H]
e
paragraph 3.5 - [H]
) with the 6 holes on the cabinet
front-plate or repeater enclosure.
2.
Secure the module in place by fastening the supplied screws into the aligned holes.
3.
Connect the CAN BUS wire (
[A]
supplied):
- if the module is mounted in the upper aperture, the CAN BUS wire must be connected between the module port
(
[B], paragraph 3.4 - [N]
,
paragraph 3.5 - [N]
) and the CAN bar port (
[C], paragraph 3.2 - [R]
)
- if the module is mounted in the lower aperture and another module is mounted in the upper aperture, the CAN BUS
wire must be connected between module port (
[D], paragraph 3.4 - [N]
,
paragraph 3.5 - [N]
) and the appropriate port
on the upper module (
[E], paragraph 3.4 - [O]
,
paragraph 3.5 - [O]
)
Attention:
The CAN BUS cables must not be connected or disconnected when the control panel is powered up.
4.
Fit the ferrite (
[F],
supplied) to the connected CAN BUS cable.
5.
Connect the Ground cable of the module (
paragraph 3.4 - [G]
and
paragraph 3.5 - [G]
) to the appropriate fitment (
[F],
paragraph 3.2 - [C]
).
6.
Complete the wiring.
D
E
E
B
C
A
B