Installation manual
Installation
51
Chapter 4
Installation
Note:
The installation of these control panels must be carried out in full compliance with national design
regulations, local fire regulations, laws and provisions in place, and in accordance with the relative
instructions and guidelines.
This Fire control panel should be located in a place that is:
• Dry
• Far from electromagnetic interference (electrical equipment, heating units, air-conditioning units, radio transmitters, etc.)
The mounting location must satisfy all the requirements of the respective laws and bylaws in force for technical
installations. When choosing the position, it is necessary to ensure that the holes for the fan in the control panel cabinet
(
paragraph 3.2 - [I]
) are not obstructed.
The system must be installed in accordance with the following procedure:
1.
Lay the cables
2.
Complete the connections on the BUS, loops and field devices
3.
Install system peripherals
4.
Mount the control panel to the wall
5.
Install accessory modules
6.
Power up the system
7.
Test the system
4.1
Mounting a PRCAB+ cabinet
1.
Remove the securing screws and door (
paragraph 3.2 - [D]
).
2.
Remove the seals from the cable entries you intend using (
paragraph 3.2 - [G]
).
Note:
In order to guarantee the IP30 protection grade, do no remove any other seals.
3.
Pull the cables through the open cable entries.
4.
Using the holes on the back, mount the cabinet to the wall (
paragraph 3.2 - [F]
).
The manufacturer strongly recommends the use of 8mm diameter minimum anchor screws (stop screws).
Note:
The equipment is suitable for mounting at heights of below 2 meters.
5.
Insert and secure the various modules inside the cabinet and on the front plate.
6.
Complete the wiring of the internal modules.
7.
Replace the front plate.