If the connection is made without fuses, positive pole have to be connected to the terminal on the left of the fuse
holders, marked as 5+. If this option is selected, input fuses of the inverter cannot be used.
1- 2- 3- 4-
5+
Terminals for the DC connection for inverters with transformer
The equipment involved are:
Ingecon
®
Sun 3.6TL U mode 208
Ingecon
®
Sun 5TL U mode 208
Ingecon
®
Sun 6TL U mode 208
Ingecon
®
Sun 3.6TL U mode 240
Ingecon
®
Sun 5TL U mode 240
Ingecon
®
Sun 6TL U mode 240
Ingecon
®
Sun 3.6TL U mode 277
Ingecon
®
Sun 5TL U mode 277
Ingecon
®
Sun 6TL U mode 277
Ingecon
®
Sun 5 U mode 208
Ingecon
®
Sun 5 U mode 240
Ingecon
®
Sun 5 U mode 277
DC connection is made by screw terminals.
One of the two poles of DC connections have to be grounded, as one of the mandatory requirements to comply with
the provisions of the National Electrical Code ANSI/NFPA70, Canadian Electrical Code CEC and other Local or State
Codes.
One to four strings can be use in DC input connection, and any of the two poles can be selected to ground, but each
different configuration requires different connections, so BE CAREFUL to follow correctly the instructions for each
configuration.
DC Input terminal strips are marked with A1, A2, A3 and A4 for one of the poles and with B1, B2, B3, B4, and B5
for the other pole.
Positive or negative pole can be chosen to connect to ground; depending of this election, DC connection will be made
in one way or another.