4.
Use a multi-purpose tester to check that there is a high impedance at the varistor terminals and
continuity at the thermal fuse terminals. Should this not be the case, any thermal fuse - varistors which
are not compliant, should be replaced.
5.
If the problem persists and the check is correct, then contact Ingeteam Inc
6.
Correctly mount the three varistors in position before closing the equipment.
8.1.3. Red LED
When this LED remains on, it indicates that the inverter is in
manual stop status.
To change to start, make it manually, because the Start or Stop
status will not change even if there is an inverter power failure.
Select
Start/Stop
option and press
to change between
start and stop.
17:32
30/04/12
17:32
30/04/12
The display shows the following message:
17:32
30/04/12
17:32
30/04/12
Click again
to confirm the option selected.
AAY2000IKI02
Ingeteam Inc
Installation manual