Wiring requirements
The correct wiring of the equipment to any PV installation will be done with the following types of wire:
AC Terminals Ingecon
®
Sun LITE U
Use 6 AWG (maximum), 90 °C (194 °F), copper wire for all AC wiring connections:
The wiring must comply with the provisions of the National Electrical Code ANSI/NFPA70, Canadian Electrical Code
CEC and other Local or State Codes.
DC Terminals Ingecon
®
Sun LITE U
Use 16 to 6 AWG (maximum), 90 °C (194 °F), copper wire for all DC wiring connections.
The wiring must comply with the provisions of the National Electrical Code ANSI/NFPA70, Canadian Electrical Code
CEC and other Local or State Codes.
Tightening torques
AC Terminals Ingecon
®
Sun LITE U
With 6/AWG, maximum tightening torque of 18.6 Nm.
DC Terminals Ingecon
®
Sun LITE U
Maximum tightening torque depending on the wiring:
Wiring
Maximum tightening torque
16/AWG
9 Nm
10/AWG
9 Nm
8/AWG
9 Nm
6/AWG
18.6 Nm
Spare parts
During the life of the Ingecon
®
Sun Lite, it might be needed to perform some maintenance that could require replacing
some parts. The parts must be the same as specified in the following list: manufacturer, model and technical
specifications:
Name
Manufacturer /
trademark
Type / model
Technical data and
securement means
Mark(s) of conformity
Fuse F1, F2
LITTLEFUSE
KLKD001.T
AC/DC Fast-acting
1 A 600 V
FERRAZ
ATM1
AC/DC Fast-acting
1 A 600 V
BUSSMAN
DCM-1
AC/DC Fast-acting
1 A 600 V
Inverter Marking
The advisory marks of the inverter are:
Grounding Terminal
RISK OF ELECTRIC SHOCK
vii
Installation manual
Ingeteam Inc