1. Overview
1.1. Introduction
The purpose of this manual is to describe the Ingecon
®
Sun Lite equipment and to provide adequate information for
its correct location, installation, start-up, maintenance and operation.
1.2. Description of the equipment
An inverter is a circuit used to convert direct current into alternating current. Ingecon
®
Sun Lite equipment therefore
serves to convert the direct current generated by the PV solar panels into alternating current to be delivered to the
electric grid.
The main models included in the Ingecon
®
Sun Lite U family are as follows:
Ingecon
®
Sun 3.6TL U mode 208
Ingecon
®
Sun 5TL U mode 208
Ingecon
®
Sun 6TL U mode 208
Ingecon
®
Sun 3.6TL U mode 240
Ingecon
®
Sun 5TL U mode 240
Ingecon
®
Sun 6TL U mode 240
Ingecon
®
Sun 3.6TL U mode 277
Ingecon
®
Sun 5TL U mode 277
Ingecon
®
Sun 6TL U mode 277
Ingecon
®
Sun 5 U mode 208
Ingecon
®
Sun 5 U mode 240
Ingecon
®
Sun 5 U mode 277
1.3. Technical data of the equipment
DC Input Ratings
Ingecon
®
Sun
3.6TL U
5 U
5TL U
6TL U
Mode
208
240
277
208
240
277
240
277
Maximum input voltage
550 Vdc
Range of input operating voltage
150 - 450 Vdc
Peak Power tracking voltage
200 - 450 Vdc
Maximum input source backfeed
current to input source
45.6 A
Total input maximum current
22 A
30 A
32 A
Fused inputs maximum current
12.5 A
AAY2000IKI02
Ingeteam Inc
Installation manual
11