AC Output
Ingecon
®
Sun
3.6TL U
5 U
5TL U
6TL U
Mode
208
240
277
208
240
277
240
277
Output power factor rating
>0.99
Operating frequency range
59.7 - 60.5 Hz
Normal output frequency
60 Hz
Maximum continuous output power
(AC)
3600 W
5000 W
6000 W
Maximum output current
17 A
25 A
26.2 A
Maximum output fault current (AC) and
duration
200 A @ 0.6 ms
Maximum output overcurrent protec-
tion
(1)
25 A
20 A
20 A
35 A
30 A
25 A
35 A
30 A
Synchronization in-rush current
5 A
Operating voltage range
183.04 -
228.8 V
211.2 -
264 V
243.76 -
304.7 V
183.04 -
228.8 V
211.2 -
264 V
243.76 -
304.7 V
211.2 -
264 V
243.76 -
304.7 V
Nominal output voltage (AC)
208 V
240 V
277 V
208 V
240 V
277 V
240 V
277 V
Maximum continuous output current
17 A
15 A
13 A
24 A
20.83 A
18.05 A
25
21.66 A
Mode
208
240
277
208
240
277
240
277
(1)
Must be provided by installer.
Output variables, trip limits and trip times:
Nominal frequency (Hz)
Trip limit (Hz)
Trip Times (s)
60
> 60.5
max 0.16
< 59.3
max 0.16
Nominal voltage (V)
Trip limit (V)
Trip Times (s)
208
104 (50%)
max 0.16
183 (88%)
max 2
228.8 (110%)
max 1
249.6 (120%)
max 0.16
240
120 (50%)
max 0.16
211.2 (88%)
max 2
264 (110%)
max 1
288 (120%)
max 0.16
277
138.5 (50%)
max 0.16
243.76 (88%)
max 2
304.7 (110%)
max 1
332.4 (120%)
max 0.16
Output variables accuracy:
Output variable
Accuracy
Voltage
1%
Frequency
0.1 Hz
Time
1%
12
Ingeteam Inc
Installation manual
AAY2000IKI02