To ensure the unit's level of protection, follow the permitted diameter range indicated in section
7.4. Connecting the potential-free auxiliary relay
These inverters have a potential-free output which can have several functions:
•
Closing the relay in the event of an insulation fault (default option).
•
Closing the relay in the event of a grid, voltage or frequency out of range alarm.
•
Closing the relay in the event of any alarm in the inverter.
•
Closing the relay upon connection of the inverter to the grid.
•
Closing the relay if the power sent to the grid by the inverter exceeds the
power setpoint
parameter. The
relay can act so that a specific charge is sent to the grid.
To connect the volt-free relay, keep in mind the relay's characteristics:
Potential-free relay's characteristics
Rated voltage
250 VAC
Nominal current
5 A
Nominal current at 30 VDC
5 A
Minimum wiring cross-section
0.2 mm
2
Maximum wiring cross-section
1.5 mm
2
Wiring diameter
4.5 ~ 10 mm
This device is connected using a conduit with at least two poles.
J39
After making the connections in the connector indicated in the previous figure, the necessary wiring for its proper
installation will leave the unit through the cable gland installed in the dedicated wiring access.
To ensure the unit's level of protection, follow the permitted diameter range indicated in section
84
Connection of accessories
Ingeteam
ABE2011IQM01_C - Installation and Operation Manual
Summary of Contents for INGECON SUN 1Play TL M
Page 58: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 108: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 309: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 310: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 312: ...Ingeteam Power Technology S A www ingeteam com ABE2011IQM01_C 06 2016...