16. Troubleshooting
This section provides a guide for troubleshooting problems that may arise in the installation and operation of the
inverter.
Troubleshooting for the inverter must be performed by qualified personnel in compliance with the
general safety instructions in this manual.
16.1. Alarms. LED messages
Alarm
LED
Lighting*
Description
Solution
Vdc1 overvoltage
Orange, 6
Overvoltage in DC input number 1
Check the connections of the PV array, ensuring the
series-parallel configuration of the panels is correct,
and that the maximum voltage of the inverter has
not been exceeded.
Vdc2 overvoltage
Orange, 6
Overvoltage in DC input number 2
Idc1 overcurrent
Red, 1
Overcurrent in DC input number 1
Check the installation in the DC part.
If the error persists, contact the Technical Service.
Idc2 overcurrent
Red, 1
Overcurrent in DC input number 2
Vbus overvoltage
Red, 2
Overvoltage in the bus
Check the connections of the PV array, ensuring the
series-parallel configuration of the panels is correct,
and that the maximum voltage of the inverter has
not been exceeded.
Inst. Overvolt. Vac
Orange, 2
Instantaneous overvoltage at the
AC output
Check the connections of the AC side. Check that
the voltage of the electricity grid is within range.
Vac out of range
Orange, 2
AC output voltage out of the
defined range
Inst. Overcurr. Iac
Red, 1
Instantaneous overcurrent at the
AC output
Check the installation in the AC part.
If the error persists, contact the Technical Service.
Iac out of range
Red, 1
AC output current out of the
defined range
Fac out of range
Orange, 3
AC grid frequency out of the
defined range
Check the connections of the AC side. Check that
the frequency of the electricity grid is within range.
DC/DC pwm fault
Red, 3
Firmware fault in the DC/DC phase
Check the installation in the DC and AC part.
If the error persists, contact the Technical Service.
DC/AC pwm fault
Red, 3
Firmware fault in the DC/AC
conversion phase
DC/DC hw fault
Red, 3
Hardware fault in the DC/DC
phase
DC/AC hw fault
Red, 3
HW fault in the DC/AC conversion
phase
Temperature alarm
Orange, 4
Temperature out of operating
range
This may be normal if the room temperature
exceeds the maximum of the unit. Check the
functioning of the fans. Protect the inverter from
direct exposure to sunlight. Cool the room where the
inverter is installed.
Fatal error
Not applicable Not applicable
Not applicable
Manual stop
Orange,
constant
The inverter has been manually
stopped.
Start the inverter by means of the display.
Hardware error
Red, 1
The inverter displays a hardware
error
Disconnect the DC and AC inverter. Wait until the
LEDs go off and re-connect. If the problem persists,
contact the Technical Service.
Residual current
Orange, 5
Residual current out of range
Check that there are no insulation faults in the PV
array. Check that the stray capacity of the PV array
does not exceed the maximum permitted.
FW update
Orange,
constant
Inverter shutdown due to firmware
load
Normal shutdown due to inverter firmware update.
105
Troubleshooting
Ingeteam
ABE2011IQM01_C - Installation and Operation Manual
DE
EN
ES
FR
IT
PT
Summary of Contents for INGECON SUN 1Play TL M
Page 58: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 108: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 309: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 310: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 312: ...Ingeteam Power Technology S A www ingeteam com ABE2011IQM01_C 06 2016...