Alarm
LED
Lighting*
Description
Solution
Grid consumption
Orange, 1
Grid consumption power out of the
permitted range
This may be due to a low irradiance level. Otherwise,
check the PV array.
Low pow. PV conn.
Orange, 1
The generated power in the PV
array is not sufficient to connect to
the AC grid
Fault elect. supply
Not applicable Not applicable
Not applicable
Idc grid injection
Not applicable Not applicable
Not applicable
Config. change
Red, 1
Inverter setting change
Normal shut down due to a change in the inverter
setting.
Isolation alarm
Orange, 5
Insulation resistance out of range
Check, on the display, that the PV array grounding is
correctly configured. Search for an insulation fault in
the PV array. If one of the poles is grounded, check
the grounding fuse.
Satur. alarm Iac
Orange, 5
AC current saturation
Check the installation in the AC part.
If the error persists, contact the Technical Service.
Low Vdc
Orange, 1
Low DC voltage
This may be due to a low irradiance level. Otherwise,
check the PV array.
Shut-off due to
burn-out
Not applicable Not applicable
Not applicable
Electric arc detection
Orange, 8
Electric arc detected in the DC
input
Not applicable
* The number of flashes is indicated.
Warnings
Alarm
LED
Lighting*
Description
Solution
Blocked fan
Orange, 7
Possible fan blockage
Check the condition of the fan and that there are no
elements that prevent it functioning properly.
High temperature
Orange, 7
Power regulation due to
temperature above operating
temperature
Check the room temperature does not exceed the
specified maximum temperature and the inverter
is not exposed to direct sunlight. Also check the
functioning of the fans.
Low temperature
Orange, 7
Temperature below operating
temperature
Check the room temperature is not below the
specified minimum temperature.
High Vdc
Not applicable Not applicable
Not applicable
String kit comm.
Not applicable Not applicable
Not applicable
Self-cons. commun.
Orange, 7
Communication fault with the self
consumption devices (wattmeter
or INGECON EMS Manager)
Check the connection of the different elements. If
the error persists, contact the Technical Service.
Surge arrester error
Not applicable Not applicable
Not applicable
* The number of flashes is indicated.
106
Troubleshooting
Ingeteam
ABE2011IQM01_C - Installation and Operation Manual
Summary of Contents for INGECON SUN 1Play TL M
Page 58: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 108: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 309: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 310: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 312: ...Ingeteam Power Technology S A www ingeteam com ABE2011IQM01_C 06 2016...