Below we can see the structure and interpretation of the variables in this menu:
Screen 1.
Pac:
Power which inverter is delivering to the grid, in W.
Vac:
Inverter output voltage (V) in the electricity grid connection.
Iac:
Inverter output current (A).
Freq:
Output current frequency to the electricity grid (Hz).
PhiCos:
Cosine of Phi Cosine of the phase shift angle between grid voltage and current supplied by the inverter.
If the phase shift is zero (0º), the cosine of phi is 1; cos 0º = 1.
Screen 2.
Vsolar:
Voltage supplied by solar panels to the inverter.
Isolar:
Current supplied by solar panels to the inverter.
Screen 3.
Alarms:
Status of inverter alarms. The meaning of the alarms is listed below:
0000H, No alarms.
0001H, Insufficient input voltage.
0002H, Grid frequency out of range.
0004H, Grid voltage out of range.
0008H, Overcurrent in the inverter bridge.
0010H, Overcurrent in the DC/DC converter.
0020H, Insulation fault.
0040H, Grid overcurrent.
0080H, Overtemperature
0100H, Bus overvoltage
0200H, Configuration change
0400H, Manual stop.
0800H, HW error
1000H, Instantaneous grid overcurrent.
2000H, Detection of island mode operation
8000H, Hardware fault alert.
The value displayed in “Inv Alarm” can be the result of the (hexadecimal) sum of two or more of the values listed
above.
E.g.: Inv Alarm = 0006H means that: The Grid Frequency and Voltage are out of range.
NumInv:
Number allocated to the inverter through the menu accessible in the display.
Cod1:
Unit operating code. This can be requested from Ingeteam’s customer services.
Cod2:
Unit operating code. This can be requested from Ingeteam’s customer services.
SN:
Serial Number.
Screen 4.
TotE:
Total energy in kWh delivered by the inverter to the grid from the date it was manufactured. Recording the
serial number of the equipment marks the start of this power log.
T.Con:
Number of hours the inverter has been connected to the grid.
Num.Con
: Number of grid connections made during all hours of operation.
Screen 5.
ParE:
Total energy in kWh delivered by the inverter to the grid since the last time the counter was reset.
Tp Con
Number of hours the inverter has been connected to the grid since the counter was last reset.
Npcon
: Number of grid connections since counter was last reset.