6.7.3. Analog Inputs – Torque (Pressure) Control
A 0 - 10 V or 4 - 20 mA signal can also be used to control the VFD torque limit setting (parameter 416) from 0 - 100% using
analog input 54. The same wiring schematics from section 6.7.2 apply with the only difference being the use of analog in-
put 54.
The VFD is set to receive a 0 - 10 V input signal as configured from the factory. To change to 4 - 20 mA input signal, toggle
the A54 switch to "U" to "I" inside the VFD.
+10 V
A IN
A IN
COM
A OUT
COM
50
53
54
55
42
39
A54
U - I
≈
5k
Ω
Drive
VFD Parameter
Description
Default Parameter
620
Terminal 54 Low Voltage
0.07 V
621
Terminal 54 High Voltage
10.00 V
622
Terminal 54 Low Current
0.14 A
623
Terminal 54 High Current
20.00 A
6.7.2. Analog Input – Speed control
A 0 - 10 V or 4 - 20 mA signal can be used to control VFD speed from 0 - 100% using analog input 53.
The VFD is set to receive a 0-10 V input signal as configured from the factory. To change to 4-20 mA input signal, toggle the
A53 switch from "U" to "I" inside the VFD.
+10V
A IN
A IN
COM
A OUT
COM
50
53
54
55
42
39
A53
U - I
0–10 V
+
-
Drive
+10 V
A IN
A IN
COM
A OUT
COM
50
53
54
55
42
39
+
-
A53
U - I
4-20mA
Drive
+10 V
A IN
A IN
COM
A OUT
COM
50
53
54
55
42
39
A53
U - I
≈
5k
Ω
Drive
VFD Parameter
Description
Default Parameter
610
Terminal 53 Low Voltage
0.07 V
611
Terminal 53 High Voltage
10.00 V
612
Terminal 53 Low Current
4 mA
613
Terminal 53 High Current
20 mA
NOTE:
Analog speed control can be used only when the VFD is in "Auto On" mode.