49
STVZSkW ed 09/08
VICTRIX ZEUS Superior kW I
Technical Documentation
Technical Documentation
The boiler reaches
and maintains the set
central heating tem-
perature.
No
Check MAX CH pa-
rameter and, if neces-
sary, adjust it until a
pressure value is ob-
tained that correspon-
ds to the requested
output.
See section D
Yes
The central heating request is satisfied.
The boiler reaches
and maintains the set
DHW temperature. No
Check that:
- the OUTPUT para-
meter corresponds to
the boiler output.
- check the MAX SPE-
ED parameter and,
if necessary, adjust it
until a pressure value
is obtained that cor-
responds to the maxi-
mum output.
See section D
Yes
The domestic hot water request is satisfied.
The burner ignites.
No
The error 01 appears on the display
(wait for the board to make 2 ignition cycles).
See error section 01 - b
No
The error 04 appears on the display
(wait for the board to make 5 ignition cycle attempts).
See error section 04.
Yes
The burner stays on after the first
10 seconds.
No
The error 01 appears on the display
(wait for the board to make 2 ignition cycles).
See error section 01 -c
Yes
The error 27 appears on the display
Yes
See error section 27
The error 02 appears on the display
Yes
See error section 02 - b
The error 03 appears on the display
Yes
See error section 03 - b
No