VICTRIX ZEUS Superior kW I
Technical Documentation
Technical Documentation
Menu configurations M5 (CONFIG).
This menu contains all
configuration options of the booiler operation parameters. (The
first entry of the various options that appears inside the parameter
is that selected by default).
M5 Menu (CONFIG)
(an access code must be introduced)
1st Level
2nd Level
Options
Description
Default value
Value set
by the
technician
P53
(POWER)
24 KW
Identifies the output of the boiler on which the P.C.B. is installed
N.B.
: in the case of boiler models called 26 kW set the parameter as: “24
KW”.
Equal to
boiler power
Equal to
boiler power
28 KW
32 KW
P54
(NTC.
TEMP.)
P54.1
DHW NTC1 Display the temperature measured by the probe on the storage tank unit
-
-
P54.2
DHW NTC 2 Not used
-
-
P54.3
NTC 3
Displays the temperature read on the return probe
-
-
P55
(CALCCHT)
Displays the C.H. flow temperature at which the boiler functions,
calculated by the active controls on system heat-adjustment
-
-
SERVICE
(BOIL.PAR.)
P57
(PUMP
SPEED)
1
First C.H. speed
AUTO
15 K
2
Second C.H. speed
3
Third C.H. speed
AUTO
Automatic pump speed. Set the ∆T value between system flow and
return (can be set from 5 to 25 K)
P62
(MAX SPEED) 4000 ÷ 5500
Set the maximum power in D.H.W. mode, setting the fan speed (in
RPM)
See page 17
P63
(MIN SPEED) 1000 ÷ 1500
Set the minimum power in D.H.W. mode, setting the fan speed (in
RPM)
See page 17
P64
(MAX CH)
≤ P62 (MAX
SPEED)
Set the maximum power in C.H. mode,. The value must be less than or
equal to "P62" (MAX. SPEED)
See page 17
P65
(MIN CH)
≥ P63 (MIN
SPEED)
Set the minimum power in C.H. mode,. The value must be less than or
equal to "P63" (MIN. SPEED)
See page 17
P66
(T.REG.
PAR.)
P66/A
(MIN. CH
T.)
Without external probe (Optional) defines the minimum flow
temperature. With the external probe present, it defines the minimum
flow temperature corresponding to operations with maximum external
temperature. (can be set from 25°C to 50°C)
N.B.:
the parameter must be confirmed in order to continue (press “D” or
exit from “P66” regulation by pressing “C”
25°C
P66/B
(MAX. CH
T.)
Without external probe (Optional) defines the maximum flow
temperature. With the external probe present, it defines the maximum
flow temperature corresponding to operations with minimum external
temperature (can be set from 50°C to 85°C)
N.B.:
the parameter must be confirmed in order to continue (press “D” or
exit from “P66” regulation by pressing “C”)
85°C
P66/C
(MIN. EXT
T.)
With external probe present it defines at which minimum external
temperature the boiler must operate at maximum flow temperature
(adjustable from -20°C to 0°C)
N.B.:
the parameter must be confirmed in order to continue (press “D” or
exit from “P66” regulation by pressing “C”)
-5°C
P66/D
(MAX. EXT
T.)
With external probe present it defines at which maximum external
temperature the boiler must operate at minimum flow temperature
(adjustable from 5°C to +25°C)
N.B.:
the parameter must be confirmed in order to continue (press “D” or
exit from “P66” regulation by pressing “C”
25°C