LUXOR
13
40 cm
Min.
100 cm
2
40 cm
40 cm
For all information and any further clarifications, refer to Stand-
ard UNI 10683:2012.
In the event of installation with other central heating appliances,
provide for suitable air inlets for each of them (according to the
instructions of each product).
It is not permitted to install the product in residential spaces:
- that have appliances supplied with liquid fuel with continuous
or discontinuous operation that take combustion air from the
room in which they are installed;
- in areas where type B gas appliances are installed to heat the
rooms, with or without production of domestic hot water, and
in adjacent or communicating rooms;
- in areas in which the measured operating negative pressure
between the external and internal technical room exceeds 4 Pa.
It is forbidden to position the product in bedrooms, bathrooms,
garages and, in general, in places with a fire risk.
Boiler room.
Check that the room meets the requirements and characteristics
of regulations in force.
The minimum volume of the room where to install the appli-
ance is indicated by the manufacturer and, however, it is greater
than 15 m
3
.
Also check that the room floor is suitable to withstand the weight
of the boiler.
It is also necessary that at least as much air as required
for regular combustion enters the room: therefore, make
openings in the room walls with a free section of at least
6 cm
2
for each kW (859.64 kcal/h) of installed thermal capacity.
The minimum section of the opening must not be less than
100 cm
2
.
The section can be calculated by using the following:
S = K * Q ≥ 100 cm
2
, where “S” is expressed in cm
2
, “Q” in kW,
“K” = 6 cm
2
/kW.
These openings must be protected by grid, wire mesh or suit-
able protection provided that the minimum cross-section is
not reduced and positioned so as to prevent them from being
obstructed.
The flow of combustion air can also be obtained from a room
adjacent to that of installation, provided that:
- said room is not used as a garage, fuel warehouse or, in any
case, for activities with fire-hazard, as a bathroom, bedroom
or common room;
- this flow is free through permanent non-closable openings,
communicating with the outside.
9
INSTALLATION ROOM FEATURES