SYSTEM MINIMUM WATER CONTENT AND PUFFER PROBE
The role of the puffer is to fulfil and meet the heat demand
peaks of the central heating system, thus reducing the ignition
and switch-off cycles, thus increasing the degree of efficiency
of the entire system.
This provides positive effects in terms of maintenance, boiler
cleaning, smoke ducts and environmental impact.
The use of the puffer/inertial storage tank is essential and man-
datory also to be able to access the Conto Termico 2.0 and must
be adjusted according to the features of the generator, with the
following capacity:
Puffer volume = 20 litres / kW.
It also allows to use the energy and heat stored inside it to feed
and meet different circuits also (e.g. room central heating / C.H.
and DHW), ensuring optimal system operation.
For this purpose, the LUXOR 16-20-24-28-33 series boilers are
supplied with a puffer probe.
The probe is linked to N.AMB connector of the control board,
reachable removing the side flank (see figure to the side).
For correct use, it must be positioned in the intermediate part
of the puffer.
For correct use, you must remove it from its original housing
and position it in the intermediate part of the puffer.
A technician’s menu is provided - with access code - to pro-
gram the puffer’s temperature (minimum values are usually
60
÷
65 °C)
.