Start-up
Start-up
Water make-up
• Activate/deactivate water make-up, select switching points for water make-up.
Water make-up is checked automatically.
•
Possible
settings:
A B C D
Automatic water make-up
þ
þ
þ
External make-up signal
þ
þ
Through RS 485-1
þ
Setting A:
Automatic water make-up is deactivated
Setting B:
Automatic water make-up is activated, integrated pressure transducer
PIS determines the switching points.
Setting C:
Automatic water make-up is activated, external make-up signal LSext
on DEC
:
pages 64 determines the switching points.
Setting D:
Automatic water make-up is activated, external make-up signal LSext
through RS 485-1 inter-face
:
pages 63–64 determines the switching points.
The top message line on the display continuously shows network information,
e.g. MSBX (
:
page 58).
IBN complete
• The system can only go into operation after all start-up steps have been
completed and confirmed.
standby
or
auto
•
standby:
Select this if the Pleno Pl_ is not to go into operation yet, but the display
function is to remain active.
•
auto:
Select this if all the requirements for start-up are present, and the Pleno Pl_
is to go into operation.
• In the
menu - Parameters
, you can change to «Initial filling» mode (
:
pages 53 | 68).
After
auto mode
has started, note the following:
• Key lock automatic after 30 min, or activate manually.
:
page 56
• When
auto
mode is started, the analogue pressure indication must be visible on the display. This appears initially in the
range from
min
(P0) to
max
(PSV).
:
page 57
Start-up is now complete. Pleno Pl_ works automatically.
• To prevent unauthorised access, the
Start-up menu
can be permanently hidden.
:
page 58