Operating -
BrainCube control
Messages
Alarms
All messages
Custom
þ
Ext. water make-up
Invers
If
þ
is selected,
messages are sent
over the output.
Message list
M01 Min pressure PIS
þ
x x
M02 Max pressure PIS
þ
x
M05 Min contents LS
x x
M06 Max contents LS
x x
M07 Check recommended
þ
x
M11 Runtime FIQ
x
M12 Leakages FIQ
x
M13 NS leaky FIQ
x
x
M14 Max quantity FIQ
x
M15 Water meter FIQ
x
M16 Press. sensor PIS
x x
M18 Pump P/K1
x x
M19 Pump P/K2
x x
M21 Voltage loss
x
M22 Standby
x
M27 Internal BrainCube
x x
messages
Output 1 / 2
1)
2)
3)
4)
4)
4)
4)
4)
4), 7)
4)
8)
5)
. . .
Example of custom selection
Defined in BrainCube
Defined in BrainCube
off
PIS > P0 + 0.1
PIS < PSV – 0.3
Acknowledge after correcting fault
Acknowledge after correcting fault
Acknowledge after maintenance
Acknowledge after correcting fault
Acknowledge after correcting fault
Acknowledge after correcting fault
Acknowledge after correcting fault
Acknowledge after correcting fault
Acknowledge after correcting fault
Acknowledge after correcting fault
Acknowledge after correcting fault
Acknowledge
Activate
auto
Acknowledge
Factory settings messages
on
PIS < P0
PIS
≥
PSV – 0.2
Insufficient flow to break tank
No flow to break tank
60 min
*
4 make-up requests within 10 min
after water make-up shut-off
FIQ counting, although make-up
not requested
Yearly make-up quantity exceeded
FIQ not counting
Fault, for example cable defect
Fuse or motor protection actuated
Fuse or motor protection actuated
Voltage loss for more than 8 h
Standby for more than 30 min
Internal fault
þ
Selected, output switches if message present.
Not selected.
x Output switches if message present, not modifiable.
* Water make-up switch-off point was not reached after 60 min run time.