I l l u s i o n - A u s t r a l i a n   M a d e   G a s   L o g   F i r e s

S.I.T  GAS VALVE: MODEL 820 NOVA mV

     
     

6

5

4

3

2

1

9

IMPORTANT: IF THE APPLIANCE CANNOT BE ADJUSTED TO OPERATE CORRECTLY,  CONTACT YOUR 

SUPPLIER AND DO NOT OPERATE THE APPLIANCE UNTIL THE PROBLEM IS RECTIFIED.

 

PRESSURE TESTING:  
 

ENSURE THE HEATER IS ISOLATED FROM THE GAS SUPPLY BY CLOSING THE MANUAL SHUTOFF VALVE DURING 

ANY PRESSURE TESTING.  

THE GAS VALVE REGULATOR CONTROLS MANIFOLD PRESSURE AND SHOULD BE CHECKED AT THE PRESSURE 

TEST POINT. (SEE BELOW)

NOTE: BOTH INLET AND MANIFOLD PRESSURES SHOULD BE CHECKED USING THE VALVE PRESSURE PORTS ON 

THE GAS VALVE.

PROCEDURE: 

 

TURN VALVE TO “

OFF”

 POSITION.

 

 

 

LOOSEN INLET PRESSURE POINT  (5)

 

 

 

ATTACH MANOMETER TO INLET PRESSURE POINT (5)

 

 

 

LIGHT THE PILOT (SEE LIGHTING INSTRUCTIONS)

 

 

 

TURN VALVE TO 

“ON” 

(WITH THERMOSTAT ON “HIGH”

)

THE PRESSURE SETTING MUST BE WITHIN THE LIMITS SPECIFIED ON THE       

COMPLIANCE PLATE LOCATED ON THE INSIDE OF THE CONTROL DOOR.

10

8

7

1.  GAS COCK KNOB

2.  HIGH LOW ADJUSTMENT

3.  PILOT BURNER ADJUSTMENT

4.  THERMOCOUPLE CONNECTION POINT

5.  OUTLET PRESSURE POINT

      6.  INLET PRESSURE POINT

       

7.  PILOT OUTLET

       

8.  MAIN GAS OUTLET

 9.  MAIN GAS INLET

10. THERMO ELECTRIC SWITCH

PRESSURE TESTING

Summary of Contents for MATRIX GFX-L

Page 1: ...ve been tested and approved in accordance with Australian Standards for installation and operation as described in this manual and have been certified by SAI GLOBAL WARNING DO NOT MODIFY THIS APPLIANC...

Page 2: ...ce has been fully tested and approved to Australian Standards NOTE MATRIX GAS LOG FIRES MODELS GFX L GFX M AND GFX S ARE DESIGNED TO BE INSTALLED IN A SUITABLY CONSTRUCTED WALL OR FIREPLACE FACADE THE...

Page 3: ...ion Matrix series of Gas Log Fires are correct at the time of printing It is always advisable to check dimensions and clearances with your Illusion dealer before commencing installation thus avoiding...

Page 4: ...gas valve THE FOLLOWING INDICATES SITUATIONS OF ABNORMAL OPERATION OF THE APPLIANCE WHEN THE APPLIANCE IS OPERATING 1 The flames appear excessively large and or sooting occurs on the logs 2 You can sm...

Page 5: ...fuel effect which is designed to operate with luminous flames and may exhibit slight carbon deposition PILOT FLAME IGNITION Depress and turn the control knob to the PILOT position Depress the button a...

Page 6: ...CONTACT WITH THE GLASS IF THE PRIMARY GUARD IS NOT FITTED ADDITIONALLY A SECONDARY FIRE SCREEN MAY BE APPROPRIATE WHEN SMALL CHILDREN OR THE INFIRM ARE IN THE VICINITY OF THE APPLIANCE WARNING DO NOT...

Page 7: ...AS NZS 5601 GAS INSTALLATIONS 2 Only an Authorised person should install the appliance 3 This appliance should be inspected prior to installation and the dealer contacted if any problems arise 4 This...

Page 8: ...127MM STAINLESS STEEL ACTIVE FLUE MUST BE USED FOR THE REAR FLUE MODEL GALVANISED STEEL MAY BE USED FOR ACTIVE FLUE ON THE VERTICAL FLUE MODEL MINIMUM OVERALL HEIGHT OF FLUE SYSTEM WHEN INSTALLED IS...

Page 9: ...M a d e G a s L o g F i r e s INSTALLATION OPTIONS 1 2 INTO FABRICATED ENCLOSURE VERTICALLY OR THROUGH REAR WALL AS 5601 AG 601 PLEASE NOTE ALL ILLusion GAS LOG FIRES MUST BE INSTALLED BY AN AUTHORIS...

Page 10: ...s L o g F i r e s INSTALLATION OPTION 3 AND 4 INTO EXISTING CHIMNEY VERTICALLY OR THROUGH REAR WALL OF CHIMNEY PLEASE NOTE ALL ILLusion GAS LOG FIRES MUST BE INSTALLED BY AN AUTHORISED PERSON IN ACCOR...

Page 11: ...og B GFX S onto the pins in the rear log and middle log as shown 7 Fit the left hand side top log onto the pins in the rear log and front lhs log as shown CHECK THE LOCATION OF ALL THE LOGS TO ENURE T...

Page 12: ...HE PRESSURE TEST POINT SEE BELOW NOTE BOTH INLET AND MANIFOLD PRESSURES SHOULD BE CHECKED USING THE VALVE PRESSURE PORTS ON THE GAS VALVE PROCEDURE TURN VALVE TO OFF POSITION LOOSEN INLET PRESSURE POI...

Page 13: ...ff the burner holes The logs should not have any sooting black areas If there is a problem call an authorised gas fitter or your local dealer 4 The appliance and flue system must be inspected by an au...

Page 14: ...RIX GFX L M S Spare Parts Spare parts are available from your supplier Refer to rear of this manual for contact details 1 2 3 4 5 6 1 Firebox body main 2 Fascia 3 Top grill assembly 4 Burner assembly...

Page 15: ...g F i r e s INSTALLATION OF FASCIAS TRIMS FLOOR MOUNT FASCIA The Wall mounted fascia is attached to the outer case assembly by locating the fascia bottom tabs A over the outer case assembly attaching...

Page 16: ...L o g F i r e s INSTALLATION OF FASCIAS WALL MOUNT FASCIA The Floor mount fascia is attached to the outer case assembly by locating the fascia bottom tabs A over the outer case assembly attaching 2 s...

Page 17: ...ergy saving method of operating the fan SHUT DOWN It will also shut down the fan 10 to 15 minutes after the heater is turned off once the firebox has cooled sufficiently REMOTE CONTROLLER OPTION The a...

Page 18: ...E CHANGED BY REMOVING THE REAR ACCESS COVER THE RECEIVER USES 4 AA BATTERIES WHICH CAN BE ACCESSED BY REMOVING THE SLIDING COVER ON THE REAR OF THE RECEIVER UNIT THE RECEIVER IS LOCATED ON THE RHS OF...

Page 19: ...ler SYMPTOM The logs have a build up of black soot in some areas POSSIBLE CAUSE Usually indicates incorrect positioning of logs if the unit has just been installed If the unit has been installed for s...

Page 20: ...Gippsland Hwy Dandenong Sth Victoria 3175 Australia Telephone 61 3 9793 7520 email service Illusionfires com au www Illusionfires com au Illusion Australia Pty Ltd reserves the right to alter specifi...

Reviews: