I l l u s i o n - A u s t r a l i a n M a d e G a s L o g F i r e s
INSTALLATION INSTRUCTIONS
NOTE THAT THIS GAS APPLIANCE MAY ONLY BE INSTALLED BY AN AUTHORISED
PERSON. CONTACT YOUR DEALER TO ARRANGE INSTALLATION.
INSTALLATION PROCEDURE
INSTALLERS CHECKLIST
1.
IMPORTANT:
BEFORE COMMENCING THE INSTALLATION, ESTABLISH THE OPTIMAL POSITION
FOR THE APPLIANCE WITH REGARD TO:
CLEARANCE FROM COMBUSTIBLE MATERIALS, POSSIBLE OBSTRUCTIONS WITHIN THE ROOF CAVITY
OR CHIMNEY, ACCESSIBILITY FOR FUTURE SERVICING, ETC:
2.
APPLIANCE & COMPONENT INSPECTION
Remove the APPLIANCE CARTON and other packaging. Inspect the appliance thoroughly to ensure it has not
been damaged in transit. Set aside the carton containing the log kit.
Check to see that the correct kit is supplied.
Open the FLUE KIT carton and check to see all components are supplied including the flue lengths, outer casing,
mounting brackets & gas cowl. Ensure that the correct flue kit for your model has been supplied.
IMPORTANT:
THE MINIMUM FLUE DIMENSIONS REQUIRED FOR THESE UNITS ARE AS FOLLOWS:
MINIMUM DIAMETER OF ACTIVE FLUE ALL MODELS IS 127MM. STAINLESS STEEL
ACTIVE FLUE MUST BE USED FOR THE REAR FLUE MODEL. GALVANISED STEEL MAY
BE USED FOR ACTIVE FLUE ON THE VERTICAL FLUE MODEL. MINIMUM OVERALL
HEIGHT OF FLUE SYSTEM WHEN INSTALLED IS 3.6 METRES (VERTICAL FLUE EXIT
MODELS) MINIMUM HORIZONTAL FLUE 300MM FOR HORIZONTAL FLUE MODELS.
(NOT INCLUDING GAS FLUE COWL ASSEMBLY)
ONLY THE CERTIFIED GAS FLUE COWL ASSEMBLY AS TESTED WITH THE APPLIANCE
MAY BE USED WITH THESE APPLIANCES.
NOTE: The Vertical flue exit models use a different gas flue cowl assembly to the
horizontal flue exit models.
FLASHING (IF REQUIRED) IS NOT INCLUDED AND MUST BE SUPPLIED BY THE INSTALLER.
3.
POSITION THE HEATER.
(ASSUMES THAT FIREPLACE OR FALSE FIREPLACE IS READY FOR THE UNIT.)
Place the heater in the required position as determined in section 1 (above).
Determine where the gas supply will be accessed.
Mark the gas pipe entry point on the wall or floor, (See DIMENSIONS page 3) and cut the hole(s).
NOTE:
It is highly recommended that a gas supply shut off valve be fitted to the gas inlet pipe outside the building
in an easily accessed position to enable the gas to be shut off in an emergency. This also makes it possible to keep
the gas supply connected to the rest of the home whilst fitting the pipe to the back of the heater prior to connecting
gas to the appliance.