4.2 Example configuration 2
Unit
LK8123 (probe length L= 472 mm)
Medium to be detected: coolant emulsion
Operating mode:
)
Installation environment: metal tank, installation to Fig. 4-2
►
Install unit.
►
Observe the distances (x), (u) and (c):
x:
min. 4.0 cm
u:
min. 1.0 cm
c:
max. 23.0 cm
►
Ground sensor and tank via an electrical
connection
.
►
Observe the maximum permitted level (b).
A distance (a2) greater than 5.0 cm has to
be observed between maximum level (b)
and mounting element.
►
Observe the parameter setting sequence:
-[OFS] = (u); e.g. (u) = 1.0 cm
-[SP1] = Set the switch point at a distance (a2)
greater than 5.0 cm below the
mounting element.
Fig. 4-2
c
b
u
a2
x
Adjustable step increment: 0.5 cm.
Switch point [SP1] is used as overflow prevention
(pump off, close inlet, ...).
►
Unit must be reinitialised:
►
Switch the operating voltage off and on again.
>
The unit is ready for operation.
►
Make further settings if necessary.
►
Check whether the unit operates correctly.