background image

The JA-187P dual zone outdoor wireless motion detector - curtain 

 

The JA-187P dual zone outdoor wireless motion detector - curtain 

MKU53900 

The JA-187P wireless outdoor detector with curtain lens characteristics is 

designed to indicate disturbances outside the building caused by human 
bodies. It is a dual zone outdoor detector by Optex with a 5° angular width 
detection zone which makes it very suitable for guarding narrow spaces 
such as balconies, French doors, terraces, etc. It is supplemented with a 
transmitter compatible with Jablotron systems. Both the detector and the 
transmitter are powered by a lithium battery. The common power supply is 
beneficial as the low battery signal is transmitted to a control panel as 
standard. The detector is equipped with three TAMPER contacts (at the front 
on the detection part and the front and rear on the transmission part), which 
immediately report opening of the detector cover or its tearing from the place 
of installation. The detector can also have the anti-masking function 
activated. The detector reports its current status via control transmissions to 
the system. 

Detector position and installation 

The following instructions should be followed when selecting the 

place for detector installation: 

 

1.  The detector should be attached to a vertical wall 
2.  The detector should be installed 0.8 – 1.2 m above the ground 
3.  The best movement detection is provided when the detection zones 

intersect 

4.  No other moving objects (bushes, trees, high grass, etc.) should be 

situated in the field of sight of the detector. Avoid direct action by 
strong sources of light (sun reflections). 

Detector 

installation 

procedure 

1. 

The detector consists 
of two parts: the 
detecting one (1) and 
the transmission one 
(2). Their mutual 
position can be 
adjusted according to 
the picture. Punch 
holes for wires in the 
plastic transmission 
part of the detector 
depending on which 
position of the parts 
you have selected 
(there are holes 
indicated on the 
plastic for this 
purpose). 

2. 

Unscrew and remove the detecting part cover. The position of the 
detecting part is fixed with a toothed plastic lug which should be 
moved upwards. Then remove the whole part with the electronics by 
bending the upper part of the plastic and pulling the swivel part 
towards you. You will thus make the installation holes located under 
this part accessible. 

 

Warning: Do not touch the sensors during handling 

 

3. 

Pull the bundle of cables through the punched hole into the 
transmission part. 

4. 

Attach the detecting and the transmission part to the wall using the 
supplied screws (mind the correct orientation – marked with an 
upward-facing arrow on the plastic). 

5. 

Reassemble the detecting part. 

6. 

Use the supplied self-adhesive plastic posts to attach the 
transmission module to the bottom of the transmission part so that the 
function switch is located in the top left corner. Place the DPS as high 
as possible – the bottom screw which attaches the plastic base to the 
wall must be visible. You will thus avoid possible interference with the 
antenna resulting in reduced detector range. 

7. 

Use connectors to interconnect the wiring between the detector parts 
(cannot be mixed up). 

8. 

If you use the rear tamper (recommended), remove the jumper from 
the pins on the board and plug in the tamper connector (regardless of 
polarity). The ring magnet included in the package should be attached 
on the wall in the corresponding position under the transmission part 
of the detector. 

Switching on and enrolling the detector 

into the system 

Study the control panel (receiver unit) installation manual before 

inserting the battery. Use AA 3.6V lithium batteries only. The correct 
position of the battery is indicated on the battery holder. When the 
battery has been installed, the transmitter sends a signal which enrolls it 
to the control panel. The control panel must be in enrollment mode at 

that time. Use switch no. 2 to set system reaction to detected movement 
(ON = instant or OFF = delay). Switch no. 1 should remain in the OFF 
position. 

 

Rear tamper
connection

Switch No. 1

INSTANT 

DELAYED

Switch No. 2

PULSE*

STATE

Vcc

TMP

INP

GND

detector

connection

LED

must be in
pulse mode

*

LI

T

H

IU

M

3 / 

3

,6V

  

A

A

 

Setting up the optical part of the detector 

A detection range of 5 m or 2 m can be set. The setting is done by turning 

the bottom detector lens (closer to the centre of the cover). The lens shape 
is designed so that its projecting part uncovers the detection distance which 
you have selected when it is inserted back into the plastic base (see the 
picture below). Do not turn the upper lens! 

 

 

 

Other detector properties can be set using a switch in the detector 

 

 

ON

 

OFF

 

test mode

normal operation 

5 sec energy saving mode 

 

120 sec 

fault signal triggers N.O

 

NC 

LED enabled

LED disabled

normal immunity of detection 

increased immunity of detection 

anti-masking enabled

 

anti-masking disabled

 

The default settings are in bold letters. 

 
The detection part can be turned in a 190° range with locking after 

each 5°. When the required angle has been set, use the plastic lug to 
prevent further movement. The angle is fixed completely when the 
cover with the lenses is put back and the screw is tightened.

  

 

 

Checking the status of and replacing batteries 

The detector checks battery status and automatically reports a low 

battery to the system. The detector remains fully functional. The 
batteries should be changed as soon as possible (within 1 week). 

The

 

control panel must be in service or maintanace mode 

before you 

start changing the battery

. Use 3.6V AA batteries only. When the 

cover has been closed, the detector switches to normal operating status 
automatically.

 

Note:

 If you insert a nearly drained battery into the detector by 

mistake, the sensor does not start working and this status is indicated 

Reviews: