31
UK
13.1 Setting values [OFS]
Table
12-1
[cm]
[inch]
Setting range
0...200.0
0...78.8
LK8122
LK8123
LK8124
LK8122
LK8123
LK8124
Step increment
0.5
1
0.2
0.5
13.2 Setting values [OP]
Table
12-2
OPx
LK8122
LK8123
LK8124
[cm]
[inch]
[cm]
[inch]
[cm]
[inch]
20.4
8.0
40.7
16.0
61
23.9
19.1
7.5
38.3
15.1
57
22.4
17.9
7.1
35.8
14.1
53
21.0
16.7
6.6
33.4
13.1
50
19.5
15.5
6.1
31.0
12.2
46
18.1
14.3
5.6
28.5
11.2
42
16.7
13.0
5.1
26.1
10.3
39
15.2
11.8
4.7
23.6
9.3
35
13.8
10.6
4.2
21.2
8.3
31
12.3
9.4
3.7
18.8
7.4
28
10.9
8.2
3.2
16.3
6.4
24
9.5
6.9
2.7
13.9
5.5
20
8.0
OPx: setting range [OP]
The indicated values for [OP] refer to the distance between OP and the
lower edge of the probe. The values apply if [OFS] = [0].
If [OFS] > [0], they increase by the set offset value.
Example LK8122: According to Table 12-2, OP has to be set to segment
20.4 cm.
[OFS] = 7.0 cm
[OP] is to be set to 20.4 cm + 7.0 cm = 27.4 cm.