39
UK
Possible cause
Recommended measures
[SC] + LED 8
+ LED 9
Flashing: short circuit in both
switching outputs
Remove the short circuit.
[PArA]
Faulty data set
.
12.5 Output response in different operating states
OUT1
OUT2*
Initialisation
OFF
OFF
Normal operation
according to the level and
ou1 setting
according to the level
4...20 mA
Fault
OFF for FOU1 = OFF;
ON for FOU1 = On
3.6 mA at FOU2 = OFF
21 mA at FOU2 = On
*) When the analogue function [ou2] = [I] is selected
13 Technical data
Technical data and scale drawing at www.ifm.com → New search → Enter
the article number.
Setting ranges
[LEnG]
mm
inch
Setting range
150...2000
6.0...78.8
Step increment
5
0.2
The setting ranges for the switching limits (SPx, rPx, FHx, FLx) depend on the
probe length (L). In general the following applies:
mm
inch
min
max
min
max
SPx / FHx
15
L - 30
0.6
L - 1.2
rPx / FLx
10
L - 35
0.4
L - 1.4
Step increment
1
0.05
• rPx / FLx is always smaller than SPx / FHx. If SPx / FHx is shifted, rPx / FLx also shifts
provided that the lower end of the setting range is not reached. Always set SPx / FHx first,
then rPx / FLx.
The setting ranges for analogue start point (ASP2) and analogue end point (AEP2)
depend on the probe length (L). In general the following applies: