For unlocking:
►
Press [
▲
] + [
▼
] simultaneously for
10 s.
> [uLoc] is displayed.
10 s
On delivery: not locked.
• Timeout:
If no button is pressed for 30 s during parameter setting, the unit returns to the
operating mode with unchanged values.
11.2 First set-up (unit with factory setting)
On delivery of the unit, you must first enter the probe length. The complete
parameter setting menu cannot be accessed before this.
Malfunctions may occur if the wrong probe length is set.
11.2.1 Entering the probe length
►
Apply operating voltage.
> Initial display
is shown.
►
Select [LEnG]
►
Press [Enter]
> [nonE] is displayed.
►
Press [
▲
] or [
▼
] for min. 1 s
> After 1 s the unit automatically displays the detected probe length
(preset function)*.
► Correct the probe length, if necessary, with [▲] or [▼]. Incrementally by
pressing the button once or continuously by keeping the button pressed.
Enter the probe length in mm. Determination of the probe length L
►
Briefly press [Enter].
* Only possible with empty tank and sufficiently large launching plate.
Then the unit changes to the operating mode.