11.6.2 Setting to another medium
►
Select [MEdI] and set:
[HIGH] =
For water and water-based media.
Operating mode is optimised for suppression of deposits on
the rod.
[MId] =
For water-based media and media with a medium DC value
(DC = dielectric constant), e.g. water-in-oil emulsions.
Operating mode optimised for the detection of media with
increased foam formation.
Note: In case of doubt carry out an application test to ensure the setting best
suited for the medium.
11.7 Simulation
11.7.1 Set simulation value
►
Select [S.LvL]
►
Set the process value to be simulated:
[Numeric
value] =
level in mm / inch (depending on the basic setting)
[FULL] =
full state
[SEnS] =
weak measured signal
[Err] =
electronic fault found
[EPTY] =
empty state
11.7.2 Set simulation time
►
Select [STim]
►
Set time span for simulation.
Setting range: 1, 2, 3, 4, 5, 10, 15, 20, 30, 45, 60 min.
Factory setting: 3 min
11.7.3 Switch simulation on / off
►
Select [S.On] and set:
[OFF] =
simulation off
[On] =
simulation on
►
Press [Enter] to start the simulation.