9
UK
5.2 Operating principle / features of the unit
The unit can be installed in tanks of different sizes. Mounting elements may also
be placed in the active measurement zone. Observe the notes on installation.
2 outputs are available. They can be set separately.
OUT1
Switching signal for level limit value / IO-Link
OUT2
Analogue signal proportional to level (invertible)
To adapt to the present application select the required operating mode.
5.2.1 Operating modes
1. Manual media selection with overflow prevention (factory setting)
Recommended:
highest operational reliability!
The medium to be detected is set manually [MEdI]. In addition, an integrated,
independently functioning overflow prevention is available.
2. Manual media selection without overflow prevention
Medium operational reliability!
The medium to be detected is set manually as described under 1. However,
the overflow prevention is deactivated. For this reason, no adjustment is
required.
3. Automatic medium detection
Lowest operational reliability!
Each time the operating voltage is switched on, the unit adjusts itself to the
medium and the installation environment.
For automatic media detection,
no
overflow prevention is available
Automatic media detection can only function properly under certain
conditions (e.g. compliance with special mounting specifications,
restrictions for operation and maintenance).