19
UK
6.2.2 Installation in the active zone
Between the maximum level (b2) and the mounting element the minimum
distance (a2) must be adhered to (fig. 6.3 and table 6-4).
►
Fix mounting elements in the mounting
zone (M) (fig. 6-1). Adhere to the
maximum permitted outside length (c)
(table 6-1 ).
►
Ensure that the maximum level (b2)
is not exceeded after completed
installation:
(b2) = (L) - (c) - (a2)
(without offset)
►
Observe further minimum distances
according to table 6-4.
Fig. 6-3
c
b2
L
u
a2
x
c: Maximum permitted outside length
(observe footnote table 6-1)
a2: Minimum distance between mounting
element and maximum level (b2).
b2: Max. level from the lower edge of
the sensor
Table
6-4
MEdI = CLW.1
MEdI = CLW.2, OIL.1
MEdI = OIL.2 / Auto
[cm]
[inch]
[cm]
[inch]
[cm]
[inch]
x
2.0
0.8
3.0
1.2
4.0
1.6
u
1.0
0.4
1.0
0.4
1.0
0.4
a2 (LK3122)
2.0
0.8
2.5
1.0
3.0
1.2
a2 (LK3123)
4.0
1.6
4.5
1.8
5.0
2.0
a2 (LK3124)
6.0
2.4
7.0
2.8
8.0
3.2
v *
)
4.5
1.8
4.5
1.8
4.5
1.8
w *
)
4.0
1.6
5.0
2.0
6.0
2.4
*) → Fig. 6-1.