The unit can be configured before or after installation.
Exception: To adjust the overflow prevention [cOP], the unit must be
installed in the tank.
10.2 Basic settings
Setting ranges of all parameters:
→ 12
Factory settings of all parameters:
→ 14
10.2.1 Set unit of measurement [uni]
►
Enter [uni] before entering the values SPx, rPx, OP or OFS.
This avoids unintentional wrong settings.
►
Select [uni]
►
Determine unit of measurement: [cm] or [inch]
uni
10.2.2 Set offset [OFS]
The distance between tank bottom and lower edge of the measuring probe can be
entered as offset value
(→ 5.6)
.
►
Set [OFS] before the values for SP1, rP1 or OP are entered.
This avoids unintentional wrong settings.
►
Select [OFS].
►
Set the value for the offset. Note the set unit of measurement [uni].
OFS
10.2.3 Set medium [MEdI]
►
Select [MEdI]
►
Set sensitivity matching the medium to be detected:
MEdI
[CLW.1] = water, hydrous media, coolant emulsions.
[CLW.2] = water, hydrous media, coolant emulsions for temperatures >
35 °C (installation in climatic tube).
[OIL.1] = oils with an increased dielectric constant (e.g. some synthetic
oils).
[OIL.2] = oils with a low dielectric constant (e.g. mineral oils).
[Auto] =
automatic medium detection.
►
In case of doubt, select [OIL.2] for oils.
►
Check proper functioning in an application test.