12.3.2 Definition “from the bottom“
Response level (z) of the overflow prevention OP from the tank bottom is defined.
• Without offset ([OFS] = [0]): [OP] = z - u
• With offset ([OFS] = u): [OP] = z
Example:
z = 18.0 cm (from the tank bottom), u = 1.0 cm
Without offset: [OP] = 18.0 cm - 1.0 cm = 17.0 cm
With offset: [OP] = 18.0 cm
Round the calculated value to the next lower adjustable value
→ 12.2
.
12.4 Setting ranges switching limits for level
Table
12-3
LK3122
LK3123
LK3124
[cm]
[inch]
[cm]
[inch]
[cm]
[inch]
[SP1] / [FH1] 2.5...20.0 1.0...8.0
3.5...39.0 1.4...15.4
6...59
2.5...23.5
[rP1] / [FL1]
2.0...19.5 0.8...7.8
3.0...38.5 1.2...15.2
5...58
2.0...23.0
Step
increment
0.5
0.2
0.5
0.2
1
0.5
The values apply if [OFS] = [0].
If OFS > 0 they increase by the set OFS value.
Example: [SP1] = 20.0 cm
[OFS] = 7.0 cm
Value displayed when the switch point is reached:
display = 20.0 cm + 7.0 cm = 27.0 cm
13 Maintenance / cleaning / change of medium
When removing or installing the unit for maintenance and cleaning:
►
Make sure that the stainless steel tube clip is fixed to the sensor.
> It must be possible to exactly reproduce the installation height and position.
►
Remove the sensor and clean it / carry out maintenance.
►
Install sensor exactly in the same position as before. Otherwise check the
parameter [OP] and carry out [cOP] once again.