11
UK
5.4 Analogue functions
The unit provides an analogue signal proportional to level. The analogue output
(OUT2) can be configured:
• [ou2] defines the output function of the analogue output: mA / V
(→ 10.3.2)
.
• In case of an internal fault, the output signal reacts according to the parameters
set in [FOU2]
(→ 10.3.8)
.
5.4.1 Curve of the analogue signal with overflow prevention:
[OP] = [value ...] (overflow prevention OP activated)
[ou2] = [I] or [U]
Fig. 5-2
Fig. 5-3
OP positioned in the upper segment.
OP shifted downward.
I [mA] / U [V]
L
20 / 10
4 / 0
A
OP
I [mA] / U [V]
L
20 / 10
4 / 0
A
OP
A: Active zone
OP: Measuring segment overflow prevention OP
L: Level
The measuring range is limited by the active measuring segment OP. If the level
reaches the measuring segment OP, the output signal jumps to its maximum value
(20 mA / 10 V).
The position of the measuring segment OP does not have any influence on
the gradient of the curve.